Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM08632
Parcel: 13321074A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08632
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A-003; EGRESS PLAN: PLEASE INDICATE THE EGRESS/EXITING AT THE PATIO (41 OCCUPANTS).
2. SHEET A-003; CALCULATIONS (MAXIMUM TRAVEL DISTANCE): THE DISTANCE INDICATED ON THE DRAWING IS 200'. THE IBC TABLE 1016.2 ALLOWS 250' FOR A SPRINKLERED 'A' OCCUPANCY. PLEASE REVISE.
3. SHEET A-003; EGRESS PLAN: A DETAIL 2A/A-806 IS INDICATED AT THE TRASH CART. PLEASE REVISE THE DETAIL REFERENCE.
4. SHEET A-111 (FLOOR PLAN); SHEET A-601 (DOOR LEGEND): EXIT DOOR 101C ON THE EAST WALL REQUIRES PANIC HARDWARE PER THE IBC SECTION 1008.1.10. PLEASE ADD TO THE DOOR LEGEND.
5. SHEET A-111; FLOOR PLAN: PLEASE INDICATE ON THE PLAN THE MINIMUM CLEAR DISTANCE OF THE INTERIOR PARTITIONS FROM THE OVEN TO THE LOCATION WHERE NON-COMBUSTIBLE WALL STUDS MAY BE USED. PLEASE INCLUDE THE OVEN MANUFACTURER'S SPECIFICATIONS.
6. SHEET A-401; ENLARGED PLAN 6: A NOTE INDICATES AN OPENING IN THE EXTERIOR WALL WILL BE REQUIRED TO BRING THE OVEN INTO THE BUILDING. IF THAT IS NOT INCLUDED IN THIS PERMIT, A REVISION WILL NEED TO BE ADDED AT A LATER DATE INDICATING THE REMOVAL AND REPLACEMENT OF THE WALL.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
01/07/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
12/10/2015 MARTIN BROWN FIRE REVIEW Approved
12/18/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed and that a notation shall be placed beneath the seal, written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Southwest Gas, the local gas utility, provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Verify the required gas pressure at the inlet for the pizza oven; the submitted listing information calls for 7" WC. Reference: Section 402.1, IFGC 2012.
3. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2012.
4. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
5. Revise the size of the fixture drain for the southern water closet in the women's restroom from 2" to 4" (P-101). Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited. Reference: Section 706.2, IPC 2012.
6. Revise the labeling for the lavatory and urinal fixture drains from "GW" to "W" (P-101).
7. Clarify the intent for the fixture drain serving the floor sink under beverage station - "GW" or "W" (P-101). Reference: Section 107.2.1, IBC 2012.
8. Provide a cleanout for the section of the building sewer located immediately downstream of the gravity grease interceptor. Reference: Section 708.3.2, IPC 2012.
9. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.
10. Show how the temperature of the hot water supply to the public lavatories is controlled (i.e. show how the specified thermostatic mixing valve is to be installed). Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.
11. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2012.
12. Appliances (e.g. soda dispensers, ice makers, tea brewers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
13. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
14. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Exception: indirect waste piping conveying only clear-water waste (e.g. effluent from a sanitizing compartment) does not require a trap. Reference: Section 802.2, IPC 2012.
15. Verify the location of the proposed indirect waste receptors at the beverage station and at the beer/wine tap are visible for inspection and have ready access for cleaning. Reference: Section 802.3, IPC 2012.
16. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
17. Provide sizing calculations for the gravity grease interceptor. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
12/18/2015 ROBERT SHERRY WATER REVIEW Completed
12/21/2015 LOREN MAKUS ENGINEERING REVIEW Approved
12/21/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
3. The exception request letter noted in flag note 3 on sheet M-111 was not found with this submittal.
4. Verify that the proposed Type I hood is equipped to automatically start the hood exhaust fan when cooking operations commence. Reference: Section 507.2.1.1, IMC 2012.
5. Show that the hood installation complies with Section 507.9, IMC 2012 with regard to a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall, and extending 18" beyond the hood.
6. Show how the proposed grease duct is to be supported and how the clearance to combustibles will be maintained. Reference: Section 304.1, IMC 2012.
12/23/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please designate panel and circuits for all luminaires on the plan. plan sheet E111. Ref: IBC sec.107.2.1, NEC art. 408.
12/29/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 6351 E. Broadway Blvd. St #129 - TI Restaurant
T15CM08632
Building Plan (1st Review)

TRANSMITTAL DATE: December 29, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning will not approve until all other PDSD agencies have approved the building plan.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956