Review Details: RESUBMITTAL - TI ALL

Permit Number - T15CM08608
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2016 MARTIN BROWN FIRE REVIEW Approved
01/28/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Section 607.1.2, IPC 2012 requires the use of a temperature mixing valve listed to ASSE 1070 to provide tempered water to lavatories in public restrooms. [Initial comment: Provide tempered water for the lavatories in public restrooms (e.g. the staff restroom); tempered water is defined as having a maximum temperature of 110 degrees Fahrenheit. Reference: Sections 416.5 and 607.1.2, IPC 2012.]
2. The specified grease interceptor (JR Smith model 8150GT) is a hydromechanical grease interceptor with a semi-automatic draw-off feature. The waste stream from the dishwasher may not discharge through this interceptor. [Initial comment: The waste stream from a dishwasher shall be routed through a grease interceptor but it may not discharge through a hydromechanical grease interceptor. Verify how the discharge from the dishwasher can be accommodated with the Pima County Regional Wastewater Reclamation Department. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.]
01/28/2016 ROBERT SHERRY WATER REVIEW Completed
02/09/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/17/2016 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/17/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved