Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T15CM08608
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 01/28/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Section 607.1.2, IPC 2012 requires the use of a temperature mixing valve listed to ASSE 1070 to provide tempered water to lavatories in public restrooms. [Initial comment: Provide tempered water for the lavatories in public restrooms (e.g. the staff restroom); tempered water is defined as having a maximum temperature of 110 degrees Fahrenheit. Reference: Sections 416.5 and 607.1.2, IPC 2012.] 2. The specified grease interceptor (JR Smith model 8150GT) is a hydromechanical grease interceptor with a semi-automatic draw-off feature. The waste stream from the dishwasher may not discharge through this interceptor. [Initial comment: The waste stream from a dishwasher shall be routed through a grease interceptor but it may not discharge through a hydromechanical grease interceptor. Verify how the discharge from the dishwasher can be accommodated with the Pima County Regional Wastewater Reclamation Department. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.] |
| 01/28/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/09/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/17/2016 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/17/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |