Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM08598
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/08/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
12/08/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The makeup air from EC-1 delivers 630 CFM less air than the exhaust fan EF-1 removes from the room. Verify that there is adequate makeup air fom other sources to make up this deficit. Reference: Section 508, IMC 2012. |
12/08/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/08/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
12/08/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
12/08/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Tucson Water does not allow meters to be manifolded to increase the water flow capacity. Verify that piping from the two 3/4" water meters is not connected. 2. Verify the presence of backflow preventers for the two water meters. 3. Determine the demand that each water meter is serving. |
12/08/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
12/08/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
12/08/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |