Permit Number: T15CM08598
Parcel: 13312006M

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08598
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2015 STEVE SHIELDS ZONING REVIEW Approved
12/08/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The makeup air from EC-1 delivers 630 CFM less air than the exhaust fan EF-1 removes from the room. Verify that there is adequate makeup air fom other sources to make up this deficit. Reference: Section 508, IMC 2012.
12/08/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/08/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
12/08/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/08/2015 ROBERT SHERRY WATER REVIEW Reqs Change 1. Tucson Water does not allow meters to be manifolded to increase the water flow capacity. Verify that piping from the two 3/4" water meters is not connected.
2. Verify the presence of backflow preventers for the two water meters.
3. Determine the demand that each water meter is serving.
12/08/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
12/08/2015 KEN BROUILLETTE FIRE REVIEW Approved
12/08/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed