Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM08563
Parcel: 133200560

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T15CM08563
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM08563
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. Provide a special inspection request form for field welding.

FOUNDATION PLANS:

1. Show compliance with termite treatment, R318.2.

SECTIONS - DETAILS:

1. Show the weep screed with a minimum clearance 4" above grade or 2" above paved areas, R703.6.2.1. Update Section 4/A4.0.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Update sections on sheet A4.0.

ELECTRICAL PLANS:

1. Show locations of each smoke alarm, R314.
2. Revise the electrical load calculations following Table E3602.2 for sizing the dwelling load. Show 3 watts per square foot of floor area. Show 1500 watts for each 20A appliance and laundry circuit. Show nameplate entries for each appliance. Apply a 40% factor for loads above 10,000 watts. Add the total nameplate for the air conditioning unit. The AC load should not be included twice. The 3,800 volt-ampere Photo Voltaic equipment only applies to a full dwelling unit rather than added living space to an existing unit.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style, or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/14/2016 EGALLET1 OUT TO CUSTOMER Completed