Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM08519
Parcel: 140122210

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08519
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2016 EGALLET1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
01/07/2016 EGALLET1 FIRE REVIEW Needs Review
01/07/2016 EGALLET1 BUILDING-COMMERCIAL REVIEW Needs Review
12/16/2015 STEVE SHIELDS ZONING REVIEW Approved
12/17/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations for the new AC units.
2. Verify that the specified thermostats provide an automatic start as described in Section C403.2.4.3.3, IECC 2012.
12/17/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
12/17/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
12/17/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify the size of the water meter (M2.1)
2. Correct the size of the cleanouts for the lavatories. (M6.1)
3. Relocate the shutoff valves for the gas service to the AC units (valve to be located upstream of the sediment trap)
12/17/2015 ROBERT SHERRY WATER REVIEW Completed