Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM08519
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2016 | EGALLET1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 01/07/2016 | EGALLET1 | FIRE | REVIEW | Needs Review | |
| 01/07/2016 | EGALLET1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 12/16/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/17/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide heating/cooling load calculations for the new AC units. 2. Verify that the specified thermostats provide an automatic start as described in Section C403.2.4.3.3, IECC 2012. |
| 12/17/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/17/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 12/17/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Verify the size of the water meter (M2.1) 2. Correct the size of the cleanouts for the lavatories. (M6.1) 3. Relocate the shutoff valves for the gas service to the AC units (valve to be located upstream of the sediment trap) |
| 12/17/2015 | ROBERT SHERRY | WATER | REVIEW | Completed |