Review Details: REVISION - - 1ST

Permit Number - T15CM08500
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Include the structural details on the drawings. [Initial comment: Provide structural calculations and details to show how the humidification units (HU 1-3 and HU 1-4) are to be connected to the building structure. Reference: Section 302.1, IMC 2012.]
2. Include the structural details on the drawings. [Initial comment: Provide structural calculations and details to show how the fan coil units (FC 1-1 and FC 1-2) are to be connected to the building structure. Reference: Section 302.1, IMC 2012.]
05/12/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/16/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/16/2016 RBENT1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2016 RBENT1 OUT TO CUSTOMER Completed