Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T15CM08500
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Include the structural details on the drawings. [Initial comment: Provide structural calculations and details to show how the humidification units (HU 1-3 and HU 1-4) are to be connected to the building structure. Reference: Section 302.1, IMC 2012.] 2. Include the structural details on the drawings. [Initial comment: Provide structural calculations and details to show how the fan coil units (FC 1-1 and FC 1-2) are to be connected to the building structure. Reference: Section 302.1, IMC 2012.] |
| 05/12/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/16/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/16/2016 | RBENT1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/16/2016 | RBENT1 | OUT TO CUSTOMER | Completed |