Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T15CM08500
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/21/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
04/19/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G1.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 2. SHEET G1.2; IBC WALL TYPES TABLE: THE FIRE WALL HOURLY RATINGS INDICATE 2, 3, AND 4 HOUR SMOKE. THE IBC TABLE 706.4 INDICATES 2, 3, AND 4 HOUR FIRE RESISTANCE RATINGS. PLEASE CLARIFY. 3. SHEET G1.2; IBC WALL TYPES TABLE: PLEASE VERIFY THE FIRE RESISTANCE RATINGS ON THIS SHEET FOR EXIT PASSAGEWAYS (SECTION 1023.3), HORIZONTAL EXITS (SECTION 1025.2), ATRIUM SEPARATION (SECTION 404.6), INCIDENTAL USE AREAS (TABLE 509), MIXED OCCUPANCIES (TABLE 508.4), AND FIRE AREA SEPARATION (TABLE 707.3.10) MATCH THE IBC REQUIREMENTS. 4. SHEET G1.3; CODE SUMMARY (ALLOWABLE AREA): PER THE IBC SECTION 506.3, THE ALLOWABLE AREA FOR THIS BUILDING (PER FLOOR) IS 23,000 + 23,000X2 = 69,000 SF. PLEASE REVISE THE DRAWING. 5. SHEET G1.3 (FIRE PROTECTION REQUIREMENTS); SHEET G1.2 (IBC WALL TYPES): THE REQUIREMENTS TABLE ON SHEET G1.3 INDICATES MOST ELEMENTS ARE NOT APPLICABLE. PLEASE COORDINATE WITH THE WALL TYPES TABLE ON SHEET G1.2, AND REMOVE ALL WALL TYPES FROM THE DRAWINGS THAT ARE NOT APPLICABLE TO THIS PROJECT. 6. SHEET G1.3; LIFE SAFETY PLAN REQUIREMENTS: REFEENCE IS MADE TO THE IBC SECTION 407.5 FOR SMOKE COMPARTMENTS. THESE ARE FOR AN I-2 OCCUPANCY GROUP. PER THE IBC SECTION 304, AMBULATORY CARE FACILITIES ARE LISTED AS A B OCCUPANCY GROUP (AND AS INDICATED ON SHEET G1.3 OCCUPANCY). PLEASE CLARIFY THE USE GROUP. 7. SHEETS G2.1, G2.2, G2.3, G2.4, AND G2.5: ARE ALL OF THE ASSEMBLIES INDICATED USED ON THIS PROJECT? PLEASE VERIFY AND REMOVE UNUSED ASSEMBLIES. 8. SHEETS G2.1, G2.2, G2.3, G2.4, AND G2.5: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 9. SHEET G4.1; LIFE SAFETY PLAN: PLEASE CLARIFY ON THE PLAN THE BOUNDARIES OF THE TWO SMOKE COMPARTMENTS. 10. SHEET G4.1; LIFE SAFETY PLAN: ARE ALL OF THE WALLS THAT ARE REQUIRED TO BE FIRE RESISTANCE RATED INDICATED AS SUCH ON THIS PLAN? PLEASE VERIFY. 11. SHEET G4.1; LIFE SAFETY PLAN: THE AREA OF REFUGE FOR EACH SMOKE COMPARTMENT INDICATES 3 NET SF X 131 OCCUPANTS. THE IBC SECTIONS 407.5.1 (FOR I-2) AND 422.3 (FOR B) INDICATE 30 NET SF/PERSON. PLEASE VERIFY. 12. SHEET G4.1: PLEASE VERIFY ON THE PLANS ALL REQUIREMENTS OF THE IBC SECTIONS 407 (FOR I-2) OR 422 (FOR B) ARE MET. 13. SHEET G4.1; LIFE SAFETY PLAN: IT APPEARS DOORS IN SEVERAL CORRIDORS DO NOT MEET THE REQUIREMENTS OF THE IBC SECTION 1005.7.1 FOR ENCROACHMENT INTO THE MEANS OF EGRESS. PLEASE VERIFY. 14. SHEET G4.2: NO REVIEW WILL BE DONE ON THIS FLOOR UNTIL A FIRST TENANT IMPROVEMENT IS SUBMITTED. 15. SHEET A0.1.2: DO THE WALLS IN SECTIONS B, G, H, AND K HAVE STRUCTURAL CALCULATIONS IN THE PREVIOUS SUBMITTAL? PLEASE VERIFY. 16. SHEET A0.1.3: DOES THE WALL IN SECTION E HAVE STRUCTURAL CALCULATIONS IN THE PREVIOUS SUBMITTAL? PLEASE VERIFY. 17. SHEET A2.1ref: ON THE DRAWINGS, PLEASE INDICATE THE QUANTITIES OF HAZARDOUS MATERIALS IN THIS BUILDING MEET THE ALLOWABLE QUANTITY REQUIREMENTS OF THE IBC TABLE 307.1(1) FOR CONTROL AREAS. INDICATE THE LOCATION OF THOSE MATERIALS ON THIS PLAN. 18. SHEETS A2.1dim, A2.1ref, AND A2.2; LEGEND: THE FOURTH SYMBOL (INDICATING A DOORWAY) INDICATES 'NEW CONSTRUCTION-EXTEND TO UNDERSIDE OF STRUCTURE ABOVE'. PLEASE REVISE THIS DESCRIPTION. 19. SHEET A7.5: THE SHEET LIST ON SHEET G1.1 DOES NOT INCLUDE THIS SHEET. PLEASE VERIFY. 20. SHEET IN2.1a: PLEASE VERIFY THIS SHEET IS NOT FOR CONSTRUCTION PER THE DRAWING NOTATION. 21. GENERAL: PLEASE VERIFY (OR REFERENCE) ON THE DRAWINGS THE MEANS OF EGRESS ILLUMINATION MEETS THE REQUIREMENTS OF THE IBC SECTION 1006. 22. GENERAL: STRUCTURAL DRAWINGS FOR THIS PROJECT WERE APPROVED ON 4-6-16. THERE WERE NO ARCHITECTURAL DRAWINGS SUBMITTED AT THAT TIME. PLEASE VERIFY ALL REFERENCES ON THE ARCHITECTURAL DRAWINGS CORRESPOND TO THE CORRECT STRUCTURAL DRAWINGS. 23. GENERAL: IT IS IMPORTANT TO DETERMINE THE OCCUPANCY CLASSIFICATION OF THE FIRST FLOOR OF THIS BUILDING. THE B OCCUPANCY FOR AMBULATORY CARE FACILITIES AS LISTED IN THE CODE SUMMARY ON SHEET G1.3 AND AS USED FOR ALLOWABLE AREAS ON THAT SAME SHEET, OR THE I-2 OCCUPANCY AS REFERENCED IN THE CODE SUMMARY ON SHEET G1.3 (SMOKE COMPARTMENT IN SECTION 407.5) AND AS REFERENCED IN THE IBC WALL TYPES FOR I-2 FACILITIES ON SHEET G1.2. FIRE RESISTANCE RATINGS AS SHOWN FOR WALLS MUST BE VERIFIED/REVISED FOR THE B OR I-2 CLASSIFICATIONS. ALLOWABLE BUILDING AREAS MUST BE VERIFIED/REVISED. IN ADDITION, THE BUILDING VALUATION AS DETERMINED AT THE ORIGINAL SUBMITTAL WILL CHANGE IF THE I-2 CLASSIFICATION BECOMES THE OCCUPANCY TYPE. PLEASE VERIFY. 24. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
04/19/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheet 2.0. (a). Provide the locations and identify all electrical panels and transformers on the floor plan. Provide for disconnecting means for the transformers as required per NEC art. 450.14. (b). As per general note A. (circuiting). Several areas between columns 2.9 through 6, are not included in the enlarged plans for circuiting ? Also identify what the encircled letter J symbolizes. (c). There is a electrical panel designated as 1L3 in room # 1010. This does not correlate with the one line diagram or panel schedules. (d). Provide a note for the electrical wiring methods to be in compliance with NEC art. 517.13 health care facilities. #2. Ref: Plan Sheets E4.0 through E5.2. (a). Provide feeder conduit and conductor sizes and types for the 600 amp panel '2H1', Elevators #1 and #2, X-Ray equipment. Ref: 2012 IBC sec. 107.2.1, 2011 NEC |
04/20/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the piping configuration for the two water heaters. Detail 3/P5.1 shows a single expansion tank serving the two water heaters but the expansion tank schedule calls for one expansion tank for each water heater. If only one expansion tank is to be installed, revise the size of the expansion tank to accommodate the total amount of store water. Reference: Sections 303.2 and 607.3, IPC 2012. 2. Coordinate the flow rate described in keynote 11 (detail 3/P5.1) with the specified flow rate shown on the recirculation pump schedule. Reference: Section 107.2.1, IBC 2012. 3. Coordinate the locations of the roof drains and overflow roof drains on the second floor roof with the architectural roof plan; revise the drainage area calculations as required. Reference: Section 107.2.1, IBC 2012. 4. Revise the location of the sediment trap for the natural gas supply to the water heaters to be downstream of the appliance shut off valve, as close to the equipment as possible in detail 3/P5.1. Reference: Section 408.4, IFGC 2012. 5. Coordinate the natural gas inputs for the AC units identified on the mechanical plans with the natural gas inputs and the unit numbers shown 6. Verify the size of the section of gas pipe serving AC 1-5. AC 1-8 and AC 1-10; 600 CFH at 350 feet requires a 2.5" pipe. Reference: Table 402.4(2), IFGC 2012. |
04/21/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify which energy code is being used. The Energy Summary on sheet G1.3 states that ASHRAE 90.1-1210 is being used but the Envelope Compliance Certificate on sheet G1.2 is based on the 2012 IECC. 2. Revise the Energy Summary on sheet G1.3 to require the U-value and SHGC of all fenestration to be NFRC-certified. Reference: Section C303.1.3, IECC 2012. 3. The Envelope Compliance Certificate indicates that the High Efficiency HVAC option has been selected as the way to comply with the "Additional Efficiency Package Requirements" (C406, IECC 2012). Revise the Mechanical Compliance Certificate to include this option. Reference: Section C401.2, IECC 2012. 4. Revise the heating and cooling load calculations, using the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson. 5. Provide structural calculations and details to show how the humidification units (HU 1-3 and HU 1-4) are to be connected to the building structure. Reference: Section 302.1, IMC 2012. 6. Provide structural calculations and details to show how the fan coil units (FC 1-1 and FC 1-2) are to be connected to the building structure. Reference: Section 302.1, IMC 2012. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/02/2016 | CPIERCE1 | APPROVAL SHELF | Completed |
05/02/2016 | CPIERCE1 | OUT TO CUSTOMER | Completed |