| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/08/2015 | KEN BROUILLETTE | FIRE | REVIEW | Passed | PLANS NEED TO BE SUBMITTED TO STATE FIRE MARSHAL'S OFFICE AT THIS IS OWNED BY PUBLIC SCHOOL DISTRICT |
| 12/22/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments, also provide a written response. #1. Provide an additional warning label per NEC art.690.17, as this possibility exists at the inverter designed with internal disconnecting means. #2. Provide for a field evaluation of a NRTL or provide verification from the manufacturer of the service equipment that the supply side bus tap at the point of the utility interconnection will not compromise the listing and performance of the service equipment. Provide a detail on the plans showing how this is to be accomplished, include all hardware used. Ref: IBC sec. 107.2.1, NEC art. 110, 300, 690, |
| 12/22/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/11/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |