Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM08316
Parcel: 12517032A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08316
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Transferring the air from the office to a different section of the egress corridor does not prevent the egress corridor from being used as a duct. [Initial comment: Provide a return grille for the southern-most new office. Reference: Section 601.2, IMC 2012.]