Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM08316
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/07/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Transferring the air from the office to a different section of the egress corridor does not prevent the egress corridor from being used as a duct. [Initial comment: Provide a return grille for the southern-most new office. Reference: Section 601.2, IMC 2012.] |