Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM08314
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/25/2015 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 11/25/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/25/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/25/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 11/25/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/25/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/25/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 11/25/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/01/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |