Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM08285
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08285
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The submitted thermostat has a manually-adjustable pre-condition feature that does not appear to provide for the automatic start-up requirement of Section C403.2.4.3.3, IECC 2012. [Second comment: Comment not addressed.] [Initial comment: Show that the new rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.]