Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08285
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Provide heating and cooling load calculations that justify the capacity of the equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.]
2. Comment not addressed. [Initial comment: Show that the new rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.]
12/22/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved