Permit Number: T15CM08285
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08285
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2015 DAVID RIVERA ZONING REVIEW Approved
11/24/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
11/25/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/25/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating and cooling load calculations that justify the capacity of the equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
2. Show that the new rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
11/25/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/25/2015 MARTIN BROWN FIRE REVIEW Approved
11/25/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/25/2015 ROBERT SHERRY WATER REVIEW Completed
12/04/2015 AROMERO4 ELECTRICAL-COMMERCIAL REVIEW Needs Review