Permit Number: T15CM08259
Parcel: 140151570

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T15CM08259
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T15CM08259
2160 E. Minorka Street
Residential (1st Review)

TRANSMITTAL DATE: December 2, 2015

The solar plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

It appears that the property dimensions are to what appears to be a fence and not the property lines.

Property dimensions are not correct.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/02/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
12/14/2015 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T15CM08259
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or a finished reproducible set. Return two sets along with a set of the first submission for reference. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets. (Do not cloud the changes made for comment revisions). Incorporate changes on originals and provide two copied sets for review.

GENERAL NOTES:
1. Provide a minimum service conductor of 100 AMP for each dwelling and conductors with minimum rating of #4 copper 75 degree C, E3602.1 & E3603.1. Panel alterations require meeting current code minimum measures. Show a service panel with feeder conductors of 100AMP rating for accepting the proposed alteration

If you have any questions please contact: