Permit Number: T15CM08217
Parcel: 12615001B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM08217
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change Smoke control is not required in 2 story atriums. Section 404.6 does not appear to allow exemption from enclosure rules for 2 story atriums.
01/21/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Girl Scouts - Leadership Building
T15CM08217
Building Plan (2nd Review)

TRANSMITTAL DATE: January 21, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. This comment was not addressed. The building elevation sheet needs to be reviewed by the Design Development Option (DDO) section and stamped prior to approval by Zoning

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/22/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the component descriptions for the exterior walls on the COMcheck Envelope Compliance Certificate to match the wall designs shown on the drawings. Clarify the 0.5 continuous R-value shown for the roof. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Include the required NFRC-certified maximum U-factor and the SHGC values for the fenestration (i.e. doors and windows) on the drawings. Reference: Section C303.1.3, IECC 2012. [Initial comment: Show that the proposed building complies with the energy code for the building envelope, the mechanical systems, the service water heating system, and the internal lighting. Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2012.]
01/22/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. This comment will be on hold until the occupancy issues for this building are approved by the building reviewer. [Initial comment: Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for assembly occupancy. See also, Section 1109.2.1, IBC 2012.]
2. Revise the calculations for the roof drainage design based on the 100-year hourly rainfall rate for Tucson, 3" per hour. The minimum sizes of gutters and downspouts shall be based on the information shown in tables 1106.6, 1106.2 (1) and 1106.2 (1), IPC 2012. (Reference: Sections 1106.1, 1106.4, and 1108.3, IPC 2012. [Initial comment: Provide location and sizing information for the gutters and downspouts. Reference: Sections 1106.1 and 1106.6, IPC 2012.]
02/05/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 2; SHEET G1.0; CODE REVIEW (SECOND FLOOR AREA): THE SECOND FLOOR AREA IS NOW LISTED AS 5017 SF WITH 29 OCCUPANTS (B OCCUPANCY), AND THE FIRST FLOOR AREA IS LISTED AS 6754 SF WITH 359 OCCUPANTS (A3 OCCUPANCY). PLEASE VERIFY THESE NUMBERS ARE CORRECT AND PROVIDE THE OCCUPANCY LOAD CALCULATIONS ON THIS SHEET FOR EACH FLOOR.
2. SHEET G1.0; PLUMBING CALCULATIONS: THE SECOND FLOOR HAS BEEN IDENTIFIED AS A B OCCUPANCY GROUP WITH 29 OCCUPANTS. PLUMBING CALCULATIONS FOR THE MEN ARE 14 OCCUPANTS/25 (SECOND FLOOR) + 179 OCCUPANTS/125 (FIRST FLOOR) = 1.99, OR 2 REQUIRED WATER CLOSETS. FOR THE WOMEN, 15 OCCUPANTS/25 (SECOND FLOOR) + 180 OCCUPANTS/65 FIRST FLOOR) = 3.4, OR 4 REQUIRED WATER CLOSETS. PLEASE INDICATE THIS CALCULATION ON THE SHEET.
3. PREVIOUS COMMENT 14; ATRIUM: THE BUILDING OFFICIAL HAS DETERMINED THE DEFINITION OF AN ATRIUM WILL ONLY BE REQUIRED WHERE AN OPENING CONNECTING 3 OR MORE STORIES THAT IS CLOSED AT THE TOP ARE PRESENT. THEREFORE, ALL OF THE IBC SECTION 404 REQUIREMENTS DO NOT APPLY TO THIS PROJECT.
4. PREVIOUS COMMENT 15; TWO WAY COMMUNICATION: PLEASE INDICATE WHERE THE TWO WAY COMMUNICATION SYSTEM IS NOTED ON THE DRAWINGS/SPECIFICATIONS.
5. PREVIOUS COMMENT 20; SHEET A202: PLEASE PROVIDE A DIMENSION ON A DRAWING INDICATING THE DISTANCE OF THE EAST WALL OF THE BUILDING IS GREATER THAN 10 FEET FROM THE PROPERTY LINE, THEREFORE NOT REQUIRING A FIRE RESISTANCE RATING.
6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments, include a written response.
#1. The written response requested for the last plan review comments ( 5 total ) only addressed comments #1 and #2.
#2. Luminaires designated as 'A', 'B', 'CC', 'L' are shown as "not used" on the luminaire schedule? Please clarify as these luminaires are shown in room #100, elevator,and exterior. Please include the rated color temperature of exterior light sources to verify compliance with section 402.1 of the Tucson Outdoor Lighting Code.
#3.It has come to the attention of the electrical plan reviewer, that the three new HP units 1-1, 1-2, 1-3, shown as new, fed from service #3,( plan sheet E5.1 ) are not in the scope of work of this project per mechanical ( plan sheet M4.2 ).
Please clarify this and adjust the plans as necessary.
Ref: IBC sec. 107.2.1