Permit Number: T15CM08217
Parcel: 12615001B

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T15CM08217
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2015 MARTIN BROWN FIRE REVIEW Reqs Change The opening between the 1st and 2nd floor appears to meet the building code definition of an atrium. Atriums have numerous specific requirements in the 2012 International Building Code. Please review section 404 and indicate on plans how all of the requirements are being addressed.
12/08/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for assembly occupancy. See also, Section 1109.2.1, IBC 2012.
2. Revise the drainage fixture units for the wash sink (WS-1) to be 2.0 drainage fixture units per each set of faucets. Reference: Table 709.1, IPC 2012.
3. The City of Tucson does not have a local amendment requiring the use of waterless urinals.
4. Clarify the location of the temperature mixing valve(s) for the wash sinks and the lavatory. Reference: Section 107.2.1, IBPC 2012.
5. Provide location and sizing information for the gutters and downspouts. Reference: Sections 1106.1 and 1106.6, IPC 2012.
12/08/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show that the proposed building complies with the energy code for the building envelope, the mechanical systems, the service water heating system, and the internal lighting. Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
3. Verify that the specified HVAC systems are provided with controls that are capable of automatically adjusting the start time of the HVAC equipment in order to bring the interior conditions to the desired temperature at the start of occupancy. Reference: Section C403.2.4.3.3, IECC 2012.
12/08/2015 ROBERT SHERRY WATER REVIEW Completed
12/14/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Girl Scouts - Leadership Building
T15CM08217
Building Plan (1st Review)

TRANSMITTAL DATE: December 14, 2015

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building elevation sheet needs to be reviewed by the Design Development Option (DDO) section and stamped prior to approval by Zoning

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/16/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
12/18/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G1.0; CODE REVIEW: THE BUILDING SETBACK REQUIREMENTS INDICATED DO NOT MATCH THE REQUIREMENTS LISTED IN THE IBC TABLE 602. PLEASE INDICATE ON THE DRAWINGS THE REQUIREMENTS PER THAT TABLE, AND ADDITIONALLY INDICATE THE ACTUAL DISTANCE.
2. SHEET G1.0; CODE REVIEW: THE SECOND FLOOR ASSEMBLY SQUARE FOOTAGE IS LISTED AS 3292. THIS DOES NOT MATCH THE SQUARE FOOTAGE SHOWN ON THE SECOND FLOOR LIFE SAFETY PLAN. PLEASE VERIFY THE SQUARE FOOTAGE AND OCCUPANT LOAD FOR THE SECOND FLOOR.
3. SHEET G1.0; SECOND FLOOR LIFE SAFETY PLAN: HALL 208 INDICATES 3082 SQUARE FEET ON THE PLAN. PLEASE VERIFY.
4. SHEET G1.0; CODE REVIEW: THE SECOND FLOOR OCCUPANT LOAD IS LISTED AS 658 OCCUPANTS. THE SECOND FLOOR LIFE SAFETY PLAN DOES NOT ACCOUNT FOR THAT MANY OCCUPANTS. PLEASE VERIFY AND REVISE AS REQUIRED.
5. SHEET G1.0; SECOND FLOOR LIFE SAFETY PLAN; CODE REVIEW: IF THE SECOND FLOOR OCCUPANT LOAD IS 658 (PER THE CODE REVIEW), THREE EXITS ARE REQUIRED PER THE IBC SECTION 1015.1.1. THIS WOULD REQUIRE THE ELEVATOR TO BE THE THIRD MEANS OF EGRESS, THEREFORE THE REQUIREMENTS OF THE IBC SECTION 1007.4 MUST BE MET. PLEASE INDICATE ON THE PLAN THOSE REQUIREMENTS.
6. SHEET G1.0; FIRST FLOOR LIFE SAFETY PLAN: PLEASE VERIFY ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTION 1028.2 FOR ASSEMBLY MAIN EXITS ARE MET.
7. SHEET G1.0; SAFETY PLANS: PLEASE VERIFY ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTION 1028.3 FOR OTHER EXITS IN ASSEMBLY ARE MET.
8. SHEET G1.0; CODE REVIEW: THE FIRST FLOOR OCCUPANT LOAD IS LISTED AS 757. THE FIRST FLOOR LIFE SAFETY PLAN DOES NOT ACCOUNT FOR THAT MANY OCCUPANTS. PLEASE VERIFY AND REVISE AS REQUIRED.
9. SHEET G1.0; FIRST FLOOR LIFE SAFETY PLAN; CODE REVIEW: IF THE FIRST FLOOR OCCUPANT LOAD IS 757 (PER THE CODE REVIEW), THREE EXITS ARE REQUIRED PER THE IBC SECTION 1015.1.1. PLEASE VERIFY.
10. SHEET G1.0; SECOND FLOOR LIFE SAFETY PLAN: PLEASE VERIFY ON THE PLAN THE STAIRWAY DOOR MEETS THE REQUIREMENTS OF THE IBC SECTION 1008.1.9.11(3).
11. SHEET G1.0; CODE REVIEW: THE PLUMBING CALCULATIONS INDICATE 539 OCCUPANTS, WHILE THE OCCUPANT LOAD CALCULATED INDICATES 1415. PLEASE CLARIFY.
12. SHEET G1.0; CODE REVIEW: PLEASE SHOW THE PLUMBING CALCULATIONS ON THE DRAWINGS FOR WATER CLOSETS, LAVATORIES, DRINKING FOUNTAINS, AND SERVICE SINK. THE REQUIREMENTS INDICATED DO NOT MATCH WHAT IS SHOWN ON THE PLANS.
13. SHEET G1.0; CODE REVIEW: A FAMILY OR ASSISTED USE TOILET IS REQUIRED PER THE IBC SECTION 1109.2.1. PLEASE INDICATE THIS ON THE DRAWINGS.
14. GENERAL: PER THE IBC CHAPTER 2, THE OPEN AREA BETWEEN THE FIRST AND SECOND FLOORS IS AN ATRIUM. VERIFY ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTION 404.4 (FIRE ALARMS), 404.6 (ATRIUM ENCLOSURE), 404.7 (STANDBY POWER), 404.8 (INTERIOR FINISH), AND 404.9 (TRAVEL DISTANCE) ARE MET.
15. GENERAL: PLEASE VERIFY ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTION 1007.8 FOR TWO WAY COMMUNICATION ARE MET.
16. SHEET A202; FIRST AND SECOND FLOOR REFERENCE PLANS: THE SOUTH WALL ELEVATION IS REFERENCED AS 1/A300. PLEASE REVISE THE REFERENCE.
17. SHEET A202; FIRST AND SECOND FLOOR REFERENCE PLANS: THE EAST WALL OF THE ENTRY COURTYARD HAS A REFERENCE 1/A206. PLEASE REVISE THE REFERENCE.
18. SHEET A202; FIRST AND SECOND FLOOR REFERENCE PLANS: THE EAST WALL OF THE LOBBY (ABOVE GRID 4) HAS A REFERENCE 1/A206. PLEASE REVISE THE REFERENCE.
19. SHEET A202; SECOND FLOOR REFERENCE PLAN: AN ENLARGED FLOOR PLAN AT THE RESTROOM/STORAGE REFERENCES 1/A207. PLEASE REVISE THE REFERENCE.
20. SHEET A202; FIRST AND SECOND FLOOR REFERENCE PLANS: THE EAST WALL OF THE BUILDING (WALL TYPE 1) AND THE WALLS ENCLOSING THE EXTERIOR STAIR (WALL TYPE 2) MUST BE INDICATED AS ONE HOUR FIRE RESISTANT RATED WALLS IN THE WALL LEGEND. PLEASE ADD A UL NUMBER TO THOSE WALLS IN THE WALL LEGEND.
21. SHEET A202; FIRST AND SECOND FLOOR REFERENCE PLANS: VERIFY THE DOORS 113 AND 114 (FIRST FLOOR) AND DOOR 202 (SECOND FLOOR) ARE FIRE RESISTANT RATED DOORS. INCLUDE A NOTE IN THE DOOR SCHEDULE (SHEET A205) THAT THE REQUIREMENTS OF THE IBC TABLE 716.5 ARE MET.
22. SHEET A202; SECOND FLOOR REFERENCE PLAN: PLEASE INDICATE THE ROOF HATCH ON THE PLAN.
23. SHEET A205; DOOR SCHEDULE: PLEASE ADD A NOTE TO THE SCHEDULE INDICATING TO SEE SHEET A209 FOR THE DOOR HARDWARE.
24. SHEET A301; CASEWORK: PLEASE VERIFY THE CASEWORK AT FAUCETS AND WORK SURFACES HAS A MAXIMUM HEIGHT OF 34" ABOVE THE FINISH FLOOR PER THE ICC/ANSI SECTION 902.4.
25. SHEET S-1.0; STRUCTURAL NOTES (FOUNDATIONS): PLEASE PROVIDE THE GEOTECHNICAL REPORT AS LISTED FOR REVIEW.
26. STRUCTURAL CALCULATIONS; SHEET 7: THE CALCULATIONS INDICATE NEW MECHANICAL UNITS ON THE EXISTING RESOURCE BUILDING. IS THIS INDICATED ON THE SUBMITTAL DOCUMENTS? PLEASE VERIFY AND ADD A NOTE OR PLAN TO THE DRAWINGS.
27. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/21/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following Electrical plan review comments, also provide a written response.
#1. Provide for GFI protection of all the kitchen 125 volt receptacles as required per NEC art. 210.8B.
#2. Identify the new 400 amp loadcenter shown on the one line diagram at service #2, plan sheet E5.2. NEC art. 408.
#3. Please clarify the new equipment to be installed at service #1. Panels 'A' and 'AC'. Why is the one line diagram and the load calc's crossed off ? If these Panels are new, is all the equipment connected new? Plan sheet E 5.2.
#4. Provide a complete luminaire schedule.
#5. Full compliance with the IECC for interior lighting.
Ref: IBC 107.2.1

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2016 AROMERO4 OUT TO CUSTOMER Completed