Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T15CM08103
Parcel: 105110690

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T15CM08103
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2016 KEN BROUILLETTE FIRE REVIEW Approved ,
01/20/2016 ROBERT SHERRY WATER REVIEW Completed
01/20/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed and that a notation shall be placed beneath the seal, written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).]
2. The submitted plumbing isometrics are illegible and the minimum font size is 3/32". [Initial comment: Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2012.]
3. The submitted metering faucet has an adjustable cycle time of 2 - 15 seconds; specify a minimum cycle time of 10 seconds. [Initial comment: Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.]
4. Delete note #2 in the water heater schedule now that the water heater will not be mounted on a wall shelf. [Initial comment: Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.]
5. Verify that the dishwasher, E52, has no valves downstream of the proposed atmospheric vacuum breaker to comply with the manufacturer's installation instructions. The iced tea brewer, E59, requires a dual check valve with an atmospheric vent that is listed to ASSE 1022; the proposed unit, a Watts LFn9 is not listed to ASSE 1022 and does not have an atmospheric vent. [Initial comment: Appliances (e.g. soda dispensers, ice makers, tea brewers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.]
6. Most of the flag note on sheet P-111 that is apparently calling for separate indirect waste pipes for each compartment of the 3-compartment sink did not print. [Initial comment: Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.]
7. Comment not addressed. [Initial comment: Verify the location of the proposed indirect waste receptor at the beverage station is visible for inspection and has ready access for cleaning. Reference: Section 802.3, IPC 2012.]
8. Two floor sinks in the grease waste system have vents that have vents that cannot [Initial comment: Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.]
01/21/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).]
2. No ventilation calculations have been added to the submitted M-601 sheet. [Initial comment: Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.]
01/21/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/25/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved