Permit Number: T15CM08103
Parcel: 105110690

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM08103
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2015 MARTIN BROWN FIRE REVIEW Reqs Change Please indicate size of CO2 tanks. Special quidelines may apply.
Clearly indicate all exit doors except main entance require panic hardware.
Add to "seperate permits" section of cover sheet -underground sprinkler supply line and kitchen exhaust hood fire suppression system.
12/03/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that in addition to signing the seal, the registrant shall include the date the document was sealed and that a notation shall be placed beneath the seal, written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Southwest Gas, the local gas utility, provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Verify the required gas pressure at the inlet for the pizza oven; the submitted listing information calls for 7" WC. Reference: Section 402.1, IFGC 2012.
3. Clarify the required gas input for the pizza oven. The submitted listing information states that the gas output is 190,000 BTUH. Reference: Section 402.2, IFGC 2012.
4. Correct the total connected load for the gas distribution system on sheet M-131. Reference: Section 402.2, IFGC 2012.
5. Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2012.
6. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
7. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.
8. Show how the temperature of the hot water supply to the public lavatories is controlled (i.e. show how the specified thermostatic mixing valve is to be installed). Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.
9. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503, 504, 606.1, 607.2, and 607.3, IPC 2012.
10. Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2012.
11. Appliances (e.g. soda dispensers, ice makers, tea brewers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
12. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
13. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Exception: indirect waste piping conveying only clear-water waste (e.g. effluent from a sanitizing compartment) does not require a trap. Reference: Section 802.2, IPC 2012.
14. Verify the location of the proposed indirect waste receptor at the beverage station is visible for inspection and has ready access for cleaning. Reference: Section 802.3, IPC 2012.
15. Verify that all of the vents (except for vents serving interceptors located outdoors) rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
12/03/2015 ROBERT SHERRY WATER REVIEW Reqs Change Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2012.
12/07/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
3. Provide calculations demonstrating adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
4. Show that the hood installation complies with Section 507.9, IMC 2012 with regard to a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall, and extending 18" beyond the hood.
5. Show how the proposed grease duct is to be supported and how the clearance to combustibles will be maintained. Reference: Section 304.1, IMC 2012.
12/11/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/11/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A-001; BUILDING CODE INFORMATION: PLEASE REVISE THE ELECTRICAL CODE TO THE 2011 NEC.
2. SHEET A-002; SITE PLAN: THE SQUARE FOOTAGE INDICATED ON THIS SHEET DOES NOT MATCH THE SQUARE FOOTAGE LISTED ON SHEET A-001. PLEASE CLARIFY.
3. SHEET A-003; EGRESS PLAN: THE NORTH EXIT IS IDENTIFIED AS 'NORTH EXIT B', WHILE ALL TRAVEL DISTANCES TO THAT EXIT INDICATE 'NORTH EXIT A'. PLEASE COORDINATE.
4. SHEET A-003; EGRESS PLAN: PLEASE INDICATE THE EXITING FROM THE OUTDOOR PATIO AREA AND IDENTIFY THE EXIT.
5. SHEET A-003; EGRESS PLAN: THIS PLAN INDICATES ACCESSIBLE SEATING IN SIX LOCATIONS. AT THOSE LOCATIONS, PLEASE SHOW THE 30" X 48" CLEAR FLOOR SPACES REQUIRED BY THE ICC/ANSI FIGURE 305.3.
6. SHEET A-111; FLOOR PLAN: THE EAST WALL OF THIS TENANT SPACE INDICATES WALL TYPE A, WHICH INDICATES ON SHEET A-801 TO BE A NON-FIRE RATED WALL. DOES THAT MEET THE REQUIREMENTS OF THE IBC SECTIONS 402.4.2.1, 708.1(3), AND 708.3? PLEASE VERIFY.
7. SHEET A-201; ELEVATION 10: PLEASE INDICATE THE PATIO AREA ON THE ELEVATION.
8. SHEET A-711; ELEVATION 15: PLEASE PROVIDE A STRUCTURAL ANALYSIS FOR THE WALL STUDS AND JOISTS THAT SUPPORT THE HOT WATER HEATER. INDICATE SIZES, CONNECTIONS, AND BRACING ON THE DRAWINGS (5/A-803) AS REQUIRED.
9. SHEET A-711; ELEVATION 15: A DETAIL REFERENCES 5B/A-800 ON THIS ELEVATION. PLEASE REVISE THAT REFERENCE NUMBER.
10. SHEET A-801; PARTITION/WALL DESIGNATIONS: WALL TYPE B INDICATES A FULL HEIGHT PARTITION, BUT SHOWS ONLY A PARTIAL HEIGHT. PLEASE REVISE.
11. SHEET A-801; PARTITION/WALL DESIGNATIONS (C AND E): A DETAIL REFERENCES 8D/A-801 AT THE DIAGONAL BRACING. PLEASE REVISE THAT REFERENCE NUMBER.
12. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/14/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied While the electrical review for the current submittal is approved, due to the potential modifications necessary to address comments associated with the reviews of other disciplines the electrical workflow is denoted as denied in order to verify that those modifications will not adversely impact the electrical review.
12/14/2015 STEVE SHIELDS ZONING REVIEW Approved
12/18/2015 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved