Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM07950
Parcel: 11704141A

Address:
601 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM07950
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2015 KEN BROUILLETTE FIRE REVIEW Approved Need current annual sprinkler and 5 year check valve inspections prior to final.
12/02/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET CVR; APPLICABLE CODES: PLEASE REVISE THE ACCESSIBILITY CODE TO THE 2009 EDITION.
2. SHEET CVR; APPLICABLE CODES: PLEASE REVISE THE IECC TO THE 2012 EDITION.
3. SHEET CVR; CODE REVIEW (ITEM 4): PLEASE REVISE THE TYPE OF CONSTRUCTION CODE REFERENCE TO THE 2012 IBC.
4. SHEET CVR: PLEASE PROVIDE THE CALCULATIONS ON THIS SHEET FOR THE PLUMBING FIXTURE REQUIREMENTS. FROM THE PLAN ON A-1.1, IT DOESN'T APPEAR WE HAVE ENOUGH WATER CLOSETS FOR WOMEN. IN ADDITION, NO HIGH/LOW DRINKING FOUNTAIN OR SINGLE POINT OF USE WATER DISPENSER WERE LOCATED ON THE PLAN. PLEASE VERIFY.
5. SHEETS De-1.1 AND De-1.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE KEY NOTES AND GENERAL NOTES.
6. SHEETS A-1.1 AND A-1.2; GENERAL NOTES AND SCOPE OF WORK: FOR NEW WALL CONSTRUCTION, PLEASE INDICATE THE SPACING OF THE WALL STUDS.
7. SHEETS A-1.1 AND A-1.2; WALL TYPES: PLEASE INDICATE THE SPACING OF THE WALL STUDS FOR ALL WALLS.
8. SHEET A-1.1 (FLOOR PLAN); SHEET CVR (NUMBER OF EXITS): THE NUMBER OF EXITS PROVIDED IS LISTED AS 3 ON SHEET CVR. PLEASE PROVIDE A PLAN THAT INDICATES THE THREE EXITS AND THE EXIT ACCESS TO EACH. VERIFY THE EXIT ACCESS TRAVEL DISTANCES DO NOT EXCEED VALUES FROM TABLE 1016.2. INCLUDE EXIT ACCESS AND TRAVEL DISTANCE FROM THE SECOND LEVEL.
9. SHEET A-1.1; FLOOR PLAN: PLEASE PROVIDE A PLAN THAT INDICATES THE EXIT DOORS MEET THE SEPARATION DISTANCE FROM EACH OTHER AS REQUIRED BY THE IBC SECTION 1015.2.1.
10. SHEET A-1.1; FLOOR PLAN: THE LANDING AREA AT THE RAMP ON THE NORTH SIDE OF THE LOBBY INDICATES STAIRS. PLEASE REVISE.
11. SHEET A-1.1; FLOOR PLAN: THE LANDING AT THE TOP OF THE RAMP ON THE NORTH SIDE OF THE LOBBY DOES NOT APPEAR TO MEET THE WIDTH REQUIREMENT (IN NORTH/SOUTH DIRECTION) SHOWN IN THE ICC/ANSI FIGURE 404.2.3.2(f). THE DIMENSION INDICATED IS 3'-10". PLEASE VERIFY.
12. SHEET A-1.1; FLOOR PLAN: THE NORTH WALL OF DESIGN ROOM 111 INDICATES A 'D' WALL TYPE (METAL STUDS TO CEILING), WHILE KEY NOTE 1 INDICATES WINDOW WALL UP TO 6'-0" ABOVE FINISH FLOOR. PLEASE CLARIFY.
13. SHEET A-1.1; FLOOR PLAN: PLEASE INDICATE ON THIS FLOOR PLAN THE FINISH FLOOR ELEVATIONS FOR THIS BUILDING AND WHERE THOSE CHANGES OCCUR.
14. SHEET A-1.3; CEILING FRAMING PLAN: PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE NEW FRAMING. IS THIS A STORAGE AREA?
15. SHEET A-1.3; DETAIL D: A NOTE INDICATES TO 'SEE STRUCTURAL DRAWINGS FOR SIZES' OF THE ANGLE LINTELS. PLEASE PROVIDE A REFERENCE TO DETAIL H ON THE DRAWINGS, ALONG WITH STRUCTURAL CALCULATIONS FOR ALL LINTELS.
16. SHEET A-1.3; DETAIL E: A NOTE FOR A 2X LEDGER IS INDICATED, BUT NO LEDGER IS SHOWN. PLEASE REVISE.
17. SHEET A-1.3; DETAIL F: A LEDGER NOTE INDICATES TO EMBED THE "J" BOLTS 6' MINIMUM. REVISE THE EMBEDMENT TO 6".
18. SHEET A-1.3; CANOPY DETAIL 1: PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE NEW CANOPY.
19. SHEET A-1.3; SECTION H: THE ELEVATION REFERENCE INDICATES B/A2. PLEASE REVISE THE REFERENCE.
20. SHEET A-2.1; RAMP DETAIL: PLEASE INDICATE THE RAMP CROSS SLOPE SHALL NOT EXCEED 1:48 PER THE ICC/ANSI SECTION 405.3, AND THE RAMP SURFACE SHALL MEET THE REQUIREMENTS OF THE ICC/ANSI SECTION 302.
21. SHEET S-3.2 (NORTH ELEVATION); SHEET A-1.1 (FLOOR PLAN): IS THE NORTH ELEVATION SHOWN ON SHEET A-3.2 CORRECT? THE FLOOR PLAN INDICATES STOREFRONT WINDOWS (NOTE 1), WHILE THE ELEVATION DOES NOT. PLEASE CLARIFY.
22. GENERAL: ALL SHEETS INDICATE 2 OF 7 IN THE TITLE BLOCK. PLEASE REVISE.
23. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide all of the construction documents required to clearly indicate the extent of the proposed work (i.e. provide M1.1). Reference: Section 107.2.1, IBC 2012.
2. Demonstrate energy code compliance for the alterations to the building envelope and mechanical systems based on the current code, IECC 2012 (i.e. provide COMcheck for the envelope and mechanical modifications). Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.
3. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. Reference: Section C303.1.3, IECC 2012.
4. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
5. The minimum seasonal energy efficiency rating (SEER) of each air conditioning unit shall comply with the requirements of Table C403.2.3 (2), IECC 2012. Reference: Section C403.2.3, IECC 2012
6. Show that each new rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012.
7. Clarify how excess outside air relief from the building is to be accomplished. Reference: Section C403.3.1.1.4, IECC 2012.
8. Show that each heat pump meets the requirements of Section C403.3.1 (economizers) unless exempted by compliance with the efficiency requirements of Table C403.3.1 (2), IECC 2012.
9. Provide the installed weight of the rooftop equipment. Reference: Section 302.1, IMC 2012.
10. Provide structural calculations and details to demonstrate that the installation of the new rooftop units will not adversely affect the structural integrity of the roof. Reference: Section 302.1, IMC 2012.
11. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
12. The submitted ventilation calculations are incomplete. Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012; for HVAC systems serving multiple zones, see Section 403.3.2.3, IMC 2012.
13. Revise the air balance for the upper level restroom so that all of the air supplied to the room is exhausted. Reference: Section 403.3, IMC 2012.
14. Provide sufficient dampers in the ductwork to ensure that the HVAC systems can be adjusted to distribute the required amount of ventilation air. Reference: Section 403.7, IMC 2012.
15. Show the location of the termination of the exhaust fan for the upper level restroom. Reference: Section 501.3.1, IMC 2012.
12/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide plans sealed by an Arizona Registrant. In addition to signing the seal, the registrant shall include the date the document was sealed and that a notation shall be placed beneath the seal, written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (See sheets P1.2 and P1.3) Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. The International Plumbing Code, 2012, is the controlling code for this activity, not the 2009 International Plumbing Code. Reference: Section 101, IBC 2012.
3. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
4. Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
5. Provide the specifications and listing information for the proposed water heater. Reference: Sections 303.2 and 501.5, IPC 2012 and Section 107.2.1, IBC 2012.
6. Provide a detail of the water heater installation, including, as applicable, the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503, 504, 606.1, 607.2, and 607.3, IPC 2012.
7. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Reference: Section C404.4, IECC 2012.
8. If the specified water heater is not supplied with integral heat traps and is not part of a hot water recirculation system, provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping. Reference: Section C404.5, IECC 2012.
9. Verify that the developed length of the hot water supply piping is fifty feet or less; if greater than fifty feet, provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012.
10. Section 604.1, IPC 2012 allows water distribution systems to be designed using accepted engineering methods. Provide the source of the method used to determine the water demand and size the water distribution system. Clarify the arithmetic used to determine the total number of water and waste fixture units.
11. Verify that the water distribution system design criterion provides a flow pressure of 15 PSI or the flow pressure prescribed by the fixture or appliance manufacturer, which ever is greater. Reference: Section 604.3, IPC 2012, as amended by the City of Tucson.
12. The plumbing schedule describes the water closets as having flush valves but the "women's sewer water diamgam (sic)" shows ¾" water supplies to each water closet (the diagram for the men's restroom does not have the pipe sizes noted). Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 3/4" Type M copper pipe has a flow velocity of 15.5 FPS. Reference: Table 604.3, IPC 2012.
13. The "men's sewer water diamgam (sic)" appears to be missing one urinal. Coordinate the riser diagrams with the plumbing plans (e.g. the women's sewer riser diamgam (sic) shows two urinals in the room and no lavatories).
12/02/2015 ROBERT SHERRY WATER REVIEW Reqs Change 1. Verify the size of the existing water meter serving this address and the total water demand it serves. Provide the serial number for the meter.
2. Provide the size of the reduced pressure backflow preventer assembly located after the water meter. Reference: Section 107.2.1, IBC 2012.
12/07/2015 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Cirrusvisual
T15CM7950
Building Plan (1st Review)

TRANSMITTAL DATE: December 7, 2015

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plan for compliance with development package DP15-0135. It appears that the building plans match the development package but unit the development is approved Zoning cannot approve the building plan.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/14/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments, also provide a written response.
#1. The plan sheets are incorrectly marked in reference to sheet letter and number.
#2. Indicate on the panel schedules New or Existing. Also some of the wording overlaps. Verify that panels are to have "Main Fuses" as stated on the panel schedule, or should it say Main Breaker?
#3. Provide a fault current chart or indicate Available Fault current at each piece of electrical equipment downstream of the ct cabinet, also indicate fuse sizes and types in the four service disconnect switches.( Riser Diagram ).
#4. Provide complete compliance with the City of Tucson/ Pima County Outdoor Lighting Code, can be downloaded at www.tucsonaz.gov/pdsd.
Ref:2012 IBC sec. 107.2.1, 2011 NEC
12/15/2015 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change DATE: December 15, 2015
DUE DATE: December 16, 2015
SUBJECT: Remodel, Parking and Landscaping
TO: Rhonda Rawson, RA
LOCATION: 601 N Stone Ave
REVIEWERS: Paul Baughman, PE, CFM
ACTIVITY: T15CM07950
SUMMARY: Engineering Division of Planning and Development Services Department has received and reviewed the proposed Development Plan Package. The main issue that needs to be addressed is the conveyance of roof drainage under the adjacent sidewalks. This requirements are being triggered due to an at least 25% increase in parking spaces.
The following items need to be addressed:
1) Approval of DP15-0135 is required prior to approval of this plans set.
2) Sheet A-3.2 has callouts for roof drains to be repainted per elevation keynote 9. This should call for roof drainage to be conveyed beneath the pedestrian way via a type 1 scupper. Please see TSM 7-01.4.3E for code requirement. There appears to be sufficient vertical fall to where this should be easy to comply with.
If you have any comments questions or wish to discuss new information, please call or email me at 520-837-5007 or paul.baughman@tucsonaz.gov.