Permit Number: T15CM07917
Parcel: 13213087F

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T15CM07917
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A3.10: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CONCESSION SCHEDULE.
04/27/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/27/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide backflow protection for each appliance (e.g. soda dispensers, ice makers, etc) connected to potable water. Reference: Sections 608.1 and 608.3, IPC 2012.
2. Provide cleanouts for each new horizontal drain. Reference: Sections 708.3.1 and 708.5, IPC 2012.
04/27/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2016 KROBLES1 OUT TO CUSTOMER Completed