Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T15CM07917
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/18/2015 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | 1. Please see copy (below) of CO2 policy. Please read and apply to this project and provide comments and corrections to plans on resubmittal.-KenB 1.0 Objectives This guideline addresses compressed gas system installations including Carbon Dioxide. The fire code official is authorized to adopt polices to clarify the application of the International Fire Code per section 104.1. This policy will go before the Fire Code Review Committee for formal adoption into the City Fire Code. 2.0 Policy These requirements shall be followed for all new installations and modifications to existing systems: Gas detection: Compressed gases such as carbon dioxide, helium, argon, nitrogen and other compressed gases that are classified as an asphyxiant shall be provided with gas detection and alarm systems. The gas detection and alarm systems shall be installed, inspected, tested, calibrated and maintained per the manufacturer's instructions or at a mini- mum annually. Records of inspectors and maintenance shall be available for review upon request by the Tucson Fire Department. Exception: A system containing fewer than two 50-pound (22 kg) DOT-approved cylinders shall not be required to provide gas detection and alarm systems. Asphyxiant gas detection systems shall be installed according to the manufacturer's manual and shall be supervised or indicate functioning power supply. The power to the gas monitoring system shall be circuit locked and labeled. The detection system shall be capable of two-tier detection; approximately 34 percent of the immediately dangerous to life and health (IDLH) concentration and approximately 75 percent of the immediately dangerous to life and health (IDLH) concentration. At approximately 34 percent of the IDLH a local warning/supervisory signal with visible and audible indication shall occur and shall be transmitted off-site as a supervisory signal when the facility has a system capable of monitoring signals off-site. At approximately 75 percent of the IDLH an evacuation alarm shall sound for the occupancy and shall transmit off-site as a gas specific alarm when the facility has a system capable of monitoring signals off site or established protocols are in place to call 911 and notify the Tucson Fire Department. Connection to fire alarm panel or monitoring panel shall be completed. A separate fire alarm permit is required. If the building does not have a monitoring panel to send a signal to an approved central, proprietary, or remote station, an established protocol shall be submitted for review for notification of the fire department upon alarm. Local warning/supervisory signal alarm and evacuation notification devices are required whether off-site monitoring is provided or not. A minimum of two evacuation notification devices with audible and visible notification shall be provided near the primary point of use and the area or room where the asphyxiant gas cylinders are located, as well as the common area where the public gathers. The notification device shall be rated a minimum of 100 CD for a visible effect and 75 dB for an audible effect. The notification devices shall be identified and labeled for the gas being used. Use of the building fire alarm notification devices for evacuation is acceptable, provided the asphyxiant gas detection has visible and audible clear indicators in the hazard area upon both the warning level and alarm level of the gas. It shall be clear to the responders upon approach to the hazard that asphyxiant gas is present. Definition: Point of use-is defined as the location where an asphyxiant gas is being used to operate a piece of equipment or machinery including, but not limited to, ketchup dispensers, carbonation machines, cup machines and drive-up windows. Specific requirements for CO2 gas systems: Where the compressed gas is carbon dioxide (CO2), the gas detection systems shall not be an oxygen sensor type. Gas detection shall be provided at each point of use whether the cylinder, vessel, or container is located inside or outside the structure. Basements or subterranean spaces, or both, that could be physically entered and that have CO2 process lines shall have gas detection. When a CO2 gas detection device reaches 15,000 ppm, a local warning or supervisory alarm shall sound at a normally occupied location, and the device shall transmit a supervisory signal when the facility has a system capable of monitoring signals off-site or established protocols are in place to notify the facility's responsible party. When a CO2 gas detection device reaches 30,000 ppm, a general evacuation signal shall sound for the occupancy, and sound for the occupancy, and the device shall transmit off-site as a gas specific alarm when the facility has a system capable of monitoring signals off-site or established protocols are in place to call 911 and notify the Tucson Fire Department. CO2 tank and piping requirements: Piping systems shall be designed, constructed and tested in accordance with ASME/ANSI B31.3, Process Piping Code,2004 edition. Piping and tubing shall be identified to indicate the material conveyed and the direction of flow. Pipe labels shall be provided at a maximum spacing of 20 feet (6096mm), at each change of direction, and on both sides of walls or floor and ceiling penetrations. The termination point of relief vent discharge piping shall be outdoors and a minimum of 10 feet (3048 mm) from operable openings into the building. Carbon dioxide piping systems shall be designed to a bursting pressure of at least four times the system design pressure. All fittings used in the piping system shall be designed for a working pressure not to exceed 125 percent of the designed pressure of the hose. All piping systems shall be leak tested in accordance with the following: 1. Piping systems shall be tested by a pneumatic pattern at a pressure equal to the working pressure for 15 minutes or as long as it takes to check each joint. The test medium shall be carbon dioxide. 2. Soap testing of all fittings shall be witnessed at time of inspection. Acceptable piping for CO2 shall be the following: 2.1. Stainless steel A269 grade, which is either seamless or welded drawn over mandrel, the following connection types: flare, welded, brazed or bite type compression. 2.2. Copper K grade, hard-drawn seamless, with the following connection types: flared, welded, brazed, bite type compression. 2.3. Copper ACR grade (1/2 inch or less) annealed seamless with the following types of connections some appraised, flared or bite that can pressure compression. 2.4. Additional approved piping and fittings can be found in CGA G6.1, Standard for Insulated Liquid Carbon Dioxide System for Consumer Site. 2.5. Rigid plastic piping shall not be allowed. A special report on the piping material shall be submitted to the Tucson Fire Department for the installation of material that is not listed in the CGA G6.1 standard, including plastic tubing. A special report on the piping material shall not be required if the piping material has been listed by a third-party testing group such as UL or FM for the intended use. CO2 gas ventilation requirements: When any ASME vessels containing CO2 or more than two 50-pound DOT CO2 cylinders per system are connected to a piping system and located within the structure, a mechanical exhaust ventilation system shall be provided. A separate plan submittal for the installation of this mechanical exhaust ventilation system is required by the Building Department. The mechanical exhaust ventilation system shall be designed at a rate not less than 1 cubic foot per minute (28316 mm3), per square foot of floor area, within the area inside the structure where the ASME vessel or DOT cylinders are located. The exhaust intake shall be taken from a point within 12 inches (305 mm) of the floor for cylinders, vessels or containers holding CO2. The exhaust system intake shall be located a minimum of 2 feet (609 mm) away from any gas detector or located on the opposite wall of any gas detector. The termination point of exhaust outlets and ducts discharging to the outdoors shall be located a minimum of 10 feet (3048 mm) from property lines, a minimum of 3 feet above the roof line, and a minimum of 10 feet from operable openings into the building and a minimum of 10 feet (3048 mm) above adjoining grade. The exhaust system shall automatically activate when the concentration of CO2 reaches 3 percent (30,000 ppm). A manual activation switch shall be provided at the entrance of the area where the ASME vessel or DOT cylinders are located. This manual activation switch shall be clearly marked with its function. Emergency relief vents, burst disks and pump vents shall be terminated outside the building and at least 10 feet from openings into the building or property lines. 3.0 Procedures These requirements will be administrated during the plan review process and inspectors will verify installation prior to finalizing the associated permit. |
11/27/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. An approved development plan is not to be used for construction of on-site utilities (e.g. water service to the building, building sewer, etc.). Provide a site plan showing the installation of the water service to the building and the installation of the building sewer, including the gravity grease interceptor. Reference: Sections 104.2 and 107.2.1, IBC 2012. 2. Provide third-party listing and material standards for all plumbing fixtures being provided by others. Reference: Sections 303.4 and 402, IPC 2012. 3. Provide an automatic faucet for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. 4. Verify that the specified water heaters are equipped with an anti-siphon device. Reference: Section 504.1, IPC 2012. 5. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2012. 6. At a minimum, water supply connections to beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1, IPC 2012. 7. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 715.1, IPC 2012, as amended by the City of Tucson. 8. Verify that separate indirect waste pipes are used for the ice makers and the ice storage bins to protect against cross-contamination or fouling. Reference: Section 801.2, IPC 2012. 9. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 10. Provide an air gap discharge for the non-potable waste from the compactor. Reference: Section 802.1.5, IPC 2012. 11. Verify the proposed indirect waste receptors located beneath appliances or millwork are visible for inspection and have ready access for cleaning. Reference: Section 802.3, IPC 2012. 12. Provide accessible cleanouts in the island sink vent system to permit rodding of all portions of the vents located below the flood rim of the fixture. Reference: Section 916.3, IPC 2012. 13. Clarify the disparities between the gas loads indicated for the rooftop units as shown on the diagram of the natural gas distribution system, the gas flows labeled on the main gas pipe sections of the natural gas distribution system, and the gas input loads shown on the mechanical schedule of the rooftop units. Reference: Section 107.2.1, IBC 2012. |
11/27/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. See the development plan for the location of the reduced pressure backflow prevention assembly and water meter. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf 2. Based on your calculations, the theater will have a demand of 125 GPM. Tucson Water limits a 2" meter to a maximum demand of 120 GPM and will not allow water meters and backflow preventers to be manifolded to achieve additional capacity. |
11/30/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size (upper and lower-case) used on the drawings to a minimum height of 3/32-inch (e.g. MEP0.2, MEP0.3, and M3.1). Reference: Section 107.2.1, IBC 2012. 2. Provide NFRC fenestration product ratings for the U-factor and the SHGC values on COMcheck or use the appropriate default U-factor and SHGC values from Tables C303.1.3 (1), C303.1.3 (2) and C303.1.3.(3), IECC 2012. (For site-assembled commercial products, the required maximum NFRC-certified U-values and SHGC may be specified on the drawings.) Reference: Section C303.1.3, IECC 2012. 3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. 4. Provide calculations to show that the ventilation system is sized in accordance with Section 403.3, IMC 2012. Reference: Section 403.2, IMC 2012 and Section C403.2.5, IECC 2012. 5. Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012. 6. If the carbon dioxide storage consists of more than two 50-pound cylinders, provide a mechanical exhaust system activated by an asphyxiant gas detection system. Reference: Tucson Fire Department Standard Operating Guideline for Compressed Gases dated 04/28/2015. 7. Positively pressurized exhaust ducts may not pass through a plenum. Reference: Section 601.4, IMC 2012. |
12/07/2015 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Theater @ Tucson Market Place T15CM7917 Building Plan (1st Review) TRANSMITTAL DATE: December 7, 2015 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Zoning has reviewed the building plan for compliance with development package DP15-0138. The plans appear to match the development package but Zoning cannot approve until all other PDSD review agencies have approved the plan. 3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
12/07/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide complete compliance with the City of Tucson / Pima County Outdoor Lighting Code. #2. Indicate feeder sizes and types for Panels 'A' and 'B'. Ref: IBC sec. 107.2.1, NEC |
12/09/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A0.00; AREA AND HEIGHT: PLEASE PROVIDE A CALCULATION ON THE DRAWINGS FOR THE ALLOWABLE HEIGHT AND AREA OF THIS BUILDING. 2. SHEET A0.00; FIRE RESISTANCE: AN ASTERISK BY THE STRUCTURAL FRAME (BEAMS, TRUSSES, AND COLUMNS) INDICATES FIRE RESISTANCE RATINGS OF PRIMARY FRAME AND BEARING WALLS ARE PERMITTED TO BE REDUCED BY ONE HOUR WHEN SUPPORTING A ROOF ONLY. PER THE IBC TABLE 601, THIS EXCEPTION APPLIES TO CONSTRUCTION TYPES IA AND IB ONLY (NOTE a). PLEASE REMOVE THAT NOTE ON THE DRAWINGS. 3. SHEET A0.00; FIRE RESISTANCE: THE ASTERISK AT THE ROOF CONSTRUCTION IS NOT APPLICABLE TO THE TYPE IIA CONSTRUCTION IN TABLE 601. ONLY NOTES b, c, AND d APPLY TO THIS PROJECT. 4. SHEET A0.00; FIRE RESISTANCE: THE TABLE ON THE DRAWINGS INDICATES ONE HOUR FIRE RESISTANT FIRE PARTITIONS. PLEASE VERIFY THE WALLS PER THE IBC SECTION 708 THAT ARE REQUIRED ON THIS PROJECT TO BE FIRE PARTITIONS. 5. SHEETS A0.20 AND A0.30: PLEASE VERIFY PROJECT NORTH ON THESE PLANS. 6. SHEETS A0.40, A0.41, AND A0.43: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE UL DESIGN VERBIAGE. 7. SHEETS A1.01 AND A1.10: PLEASE VERIFY PROJECT NORTH ON THESE PLANS. 8. SHEET A2.10; FLOOR PLAN: IS THE 'PROJECT NORTH' INDICATED ON THIS SHEET CORRECT? IF SO, THE FOUR EXTERIOR ELEVATION REFERENCES (03, 04, 05, AND 06 ON SHEET A7.01) ARE NOT CORRECT. PLEASE VERIFY. 9. SHEET A2.11 (FLOOR PLAN); SHEET A2.13 (FLOOR PLAN): PLEASE INDICATE ON THE PLAN (15/A3.32) THAT THE DOORS OPENING INTO THE CORRIDOR BETWEEN GRIDS 5 AND 6 (AUDITORIUMS 5 AND 6 ON A2.11) DO NOT REDUCE THE CORRIDOR WIDTH BY MORE THAN IS ALLOWED IN THE IBC SECTION 1005.7.1. 10. SHEET A3.20; RESTROOM PLAN 03: IN THE MEN'S RESTROOM, PLEASE VERIFY ON THE PLANS THE MANEUVERING REQUIREMENTS OF THE ICC/ANSI FIGURE 305.7(a) ARE MET AT THE URINALS. 11. GENERAL: PLEASE VERIFY PROJECT NORTH ON ALL PLANS IN THIS PROJECT. 12. GENERAL: PLEASE VERIFY ON THE PLANS THE REQUIREMENTS OF THE IBC SECTION 714 FOR PENETRATIONS THROUGH HORIZONTAL ASSEMBLIES AND OTHER FIRE RESISTANT ASSEMBLIES ARE MET. 13. GENERAL: PLEASE VERIFY ON THE PLANS THE REQUIREMENTS OF THE IBC SECTION 716 FOR OPENING PROTECTIVES ARE MET. 14. GENERAL: PLEASE VERIFY ON THE PLANS THE REQUIREMENTS OF THE IBC SECTION 717 FOR DUCTS AND AIR TRANSFER OPENINGS ARE MET. 15. GENERAL: PLEASE VERIFY ON THE PLANS THE REQUIREMENTS OF THE IBC SECTION 718 FOR CONCEALED SPACES ARE MET. 16. GENERAL: PLEASE VERIFY ON THE PLANS THE REQUIREMENTS OF THE IBC SECTION 907.2.1.1 FOR FIRE ALARM SYSTEM INITIATION ARE MET. 17. GENERAL: PLEASE VERIFY ON THE PLANS THE REQUIREMENTS OF THE IBC SECTION 909 FOR SMOKE CONTROL SYSTEMS ARE MET. 18. GENERAL: PLEASE VERIFY ON THE PLANS THE REQUIREMENTS OF THE IBC SECTION 1006 FOR MEANS OF EGRESS ILLUMINATION ARE MET. 19. GENERAL: PLEASE VERIFY ON THE PLANS THE REQUIREMENTS OF THE IBC SECTION 409 FOR PROJECTION ROOMS OR AREAS ARE MET, INCLUDING VENTILATION AND LIGHTING. 20. GENERAL: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE ALL SHEETS AS REQUIRED. 21. SHEETS S1.01 AND S1.02: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE GENERAL STRUCTURAL NOTES. 22. SHEET S4.01; PRECAST PANEL KEY PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE PANEL IDENTIFICATION MARKS. 23. GENERAL: BELOW THE ENGINEER'S SEAL ON EACH STRUCTURAL SHEET, PLEASE ADD THE EXPIRATION DATE OF THAT LICENSE. 24. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
12/10/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
12/15/2015 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/17/2015 | EGALLET1 | OUT TO CUSTOMER | Completed |