Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - RES
Permit Number - T15CM07890
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/18/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
12/01/2015 | DSANTAC2 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Please address the following plan review comments. #1. Please provide the following information for the POWERBLASTER CT modules. (a). Listing information to verify the installations in service panels so as to not compromise the listing of the panels utilizing this device. (b). Include or show the device on the one or three line diagram. (c). Explain the function of this device or equipment. #2. Also the warning label "WARNING electric shock hazard do not touch terminals, terminals on both line and load sides may be energized in the off position" Should be installed on the inverters as this hazard exists at this location. Ref: 2012 IRC, 2011 NEC, 2012 IBC. |
12/02/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved |