Permit Number: T15CM07800
Parcel: 141018940

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM07800
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2015 STEVE SHIELDS ZONING REVIEW Approved
11/09/2015 ROBERT SHERRY WATER REVIEW Completed
11/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/09/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
11/09/2015 KEN BROUILLETTE FIRE REVIEW Approved
11/12/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide an accessible counter surface in accordance with ANSI A117.1
2. Clarify notation on floor plan sheet that does not apply to this project
11/12/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide ventilation calculations for each unit and space. Reference: Section 403.3, IMC 2012 (not ASHRAE 62.1)
2. Provide balancing information.
3. Provide a path for the air return to each unit that goes through the unit filter.
11/12/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide circuit and panel designations for the lighting.
Also provide full compliance with the 2012 IECC.
Ref: IBC sec. 107.2.1, NEC art. 408.
12/08/2015 EGALLET1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review