Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM07800
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/09/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/09/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/09/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 11/09/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 11/12/2015 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide an accessible counter surface in accordance with ANSI A117.1 2. Clarify notation on floor plan sheet that does not apply to this project |
| 11/12/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide ventilation calculations for each unit and space. Reference: Section 403.3, IMC 2012 (not ASHRAE 62.1) 2. Provide balancing information. 3. Provide a path for the air return to each unit that goes through the unit filter. |
| 11/12/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide circuit and panel designations for the lighting. Also provide full compliance with the 2012 IECC. Ref: IBC sec. 107.2.1, NEC art. 408. |
| 12/08/2015 | EGALLET1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |