Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T15CM07752
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/08/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/14/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 12/21/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The comment does not appear to have been addressed; Add a note to the plumbing drawings stating that the sensor-operated faucets will be set to operate for at least 10-seconds and no longer than 30-seconds (0.25 Gallons). [Initial comment: Verify that the automatic faucets for the lavatory will be set to operate for a minimum time of 10-seconds and to dispense a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.] |
| 12/21/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The City of Tucson has not adopted ASHRAE Standard 62-1 as an approved method for calculating ventilation requirements. Table 403.3 provides a category of "Dressing rooms" under the general occupancy classification of "Retail stores, sales floors and showroom floors"; no locker rooms are included in this occupancy classification. "Locker rooms" and "Sports locker rooms" are found under the education occupancy classification. [Initial comment: Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012.] |
| 12/30/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |