Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T15CM07752
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2015 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | Access to the required 2nd access does not appear to meet Section 1014.2 (4) exception 2 (2.4). Please indicate how this project will comply with that section. |
| 11/24/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET C0-0; CODE INFORMATION: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE SQUARE FOOTAGE TABLE. 2. SHEET C0-0; CODE INFORMATION: INDICATE THE ICC/ANSI 117.1 IS THE 2009 EDITION. 3. SHEET A1-0c; FLOOR PLAN: PER THE IBC SECTION 1014.2, MEANS OF EGRESS IN GROUP M OCCUPANCIES ARE NOT PROHIBITED THROUGH STOCKROOMS IF THE REQUIREMENTS OF EXCEPTION 2 ARE MET. IT DOES NOT APPEAR 2.4 REQUIREMENTS ARE MET (PARTIAL HEIGHT FIXED WALLS). PLEASE VERIFY. 4. SHEET A1-2; FLOOR PLAN: NOTE LP25 IS CROSSED OUT IN THE TABLE, BUT IS INDICATED IN TWO LOCATIONS ON THE PLAN. PLEASE CLARIFY. 5. SHEET A2-0: ARE THESE ELEVATION INDICATORS LOCATED ON A BUILDING PLAN? PLEASE VERIFY AND PROVIDE AS REQUIRED. 6. SHEETS A3-0 AND A3-1: ARE THESE ELEVATION INDICATORS LOCATED ON A BUILDING PLAN? PLEASE VERIFY AND PROVIDE AS REQUIRED. 7. SHEET A4-0; DETAIL 4: PLEASE PROVIDE A BRACING SIZE ON THIS DETAIL. 8. SHEET A4-0; DETAIL 12: PER THE IBC SECTION 708.4, THE FIRE PARTITION SHALL EXTEND TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE OR TO A HORIZONTAL RATED ASSEMBLY ABOVE. IT DOES NOT APPEAR THIS PARTITION MEETS THAT REQUIREMENT. PLEASE VERIFY. 9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 11/24/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 11/24/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the automatic faucets for the lavatory will be set to operate for a minimum time of 10-seconds and to dispense a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. |
| 11/24/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide exhaust for the fitting rooms. Reference: Section 403.3, IMC 2012. |
| 12/02/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Denied | While the electrical review for the current submittal is approved, due to the potential modifications necessary to address comments associated with the reviews of other disciplines the electrical workflow is denoted as denied in order to verify that those modifications will not adversely impact the electrical review. |