Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM07718
Parcel: 136214840

Address:
3630 S LOGAN AV

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T15CM07718
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2015 DAVID RIVERA ZONING REVIEW Approved
11/30/2015 DSANTAC2 BUILDING-RESIDENTIAL REVIEW Reqs Change #1.Please provide the necessary information to confirm the "CANOPY" rail or racking system meets code and listing requirements for equipment grounding as required per NEC art. 690.43C.
#2. Also the warning label "WARNING electric shock hazard do not touch terminals, terminals on both line and load sides may be energized in the off position". Should be installed on the inverters as this hazard exists at this location.
#3. Please provide the following information for the POWERBLASTER CT modules.
(a). Listing information to verify the installations in service panels so as to not compromise the listing of the panels utilizing this device.
(b). Include or show the device on the one or three line diagram.
(c). Explain the function of this device or equipment.
Ref: IRC, IBC, NEC.
12/02/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved