Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - RES
Permit Number - T15CM07715
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 11/30/2015 | DSANTAC2 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Please address the following plan review comments. #1.Please provide the necessary information to confirm the "CANOPY" rail or racking system meets code and listing requirements for equipment grounding as required per NEC art. 690.43C. #2. Also the warning label "WARNING electric shock hazard do not touch terminals, terminals on both line and load sides may be energized in the off position" Should be installed on the inverters as this hazard exists at this location. #3. Please clarify what the numbered triangles below the electrical equipment designate, Plan sheet PV 5. #4. Please provide the following information for the POWERBLASTER CT modules. (a). Listing information to verify the installations in service panels so as to not compromise the listing of the panels utilizing this device. (b). Include or show the device on the one or three line diagram. (c). Explain the function of this device or equipment. Ref: 2012 IRC, 2011 NEC, 2012 IBC. |
| 12/02/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved |