Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - RES
Permit Number - T15CM07713
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 11/30/2015 | DSANTAC2 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Please address the following plan review comments. #1. Please provide additional information on the plan documents that clarifies what the numbered triangles below the electrical equipment designates. Plan sheet PV6. #2. Also the warning label "WARNING electric shock hazard do not touch terminals, terminals on both line and load sides may be energized in the off position" Should be installed on the inverters as this hazard exists at this location. #3. Please provide the following information for the POWERBLASTER CT modules. (a). Listing information to verify the installations in service panels so as to not compromise the listing of the panels utilizing this device. (b). Include or show the device on the one or three line diagram. (c). Explain the function of this device or equipment. Ref : IRC, NEC, IBC |
| 12/02/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved |