Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM07711
Parcel: 140120720

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T15CM07711
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2015 DAVID RIVERA ZONING REVIEW Approved
12/01/2015 DSANTAC2 BUILDING-RESIDENTIAL REVIEW Reqs Change Please address the following plan review comments.
#1. Provide information or more detail for the PV panel racking system or structure .Ensure compliance with 690.43C
#2. Also the warning label ,"WARNING electric shock hazard do not touch terminals, terminals on both line and load sides may be energized in the off position". Should be installed on the inverters as this hazard exists at this location.
#3. Please provide the following information for the POWERBLASTER CT modules.
(a). Listing information to verify the installations in service panels so as to not compromise the listing of the panels utilizing this device.
(b). Include or show the device on the one or three line diagram.
(c). Explain the function of this device or equipment.


Ref: 2012 IRC, 2011 NEC, 2012 IBC.
12/02/2015 PAUL BAUGHMAN ENGINEERING REVIEW Reqs Change Needs a floodplain use permit and valuation of the work.