Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM07710
Parcel: 136332760

Address:
9049 E ARBOR ST

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - RES

Permit Number - T15CM07710
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2015 DAVID RIVERA ZONING REVIEW Approved
12/01/2015 DSANTAC2 BUILDING-RESIDENTIAL REVIEW Reqs Change Please address the following plan review comments.
#1. Provide information or more detail for the PV panel racking system or structure .Ensure compliance with 690.43C
#2. Also the warning label ,"WARNING electric shock hazard do not touch terminals, terminals on both line and load sides may be energized in the off position". Should be installed on the inverters as this hazard exists at this location.
Ref: 2012 IRC, 2011 NEC, 2012 IBC.
12/02/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved