Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - RES
Permit Number - T15CM07710
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 12/01/2015 | DSANTAC2 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Please address the following plan review comments. #1. Provide information or more detail for the PV panel racking system or structure .Ensure compliance with 690.43C #2. Also the warning label ,"WARNING electric shock hazard do not touch terminals, terminals on both line and load sides may be energized in the off position". Should be installed on the inverters as this hazard exists at this location. Ref: 2012 IRC, 2011 NEC, 2012 IBC. |
| 12/02/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved |