Permit Review Detail
Review Status: Completed
Review Details: PLANS OK TO SUBMIT - RES
Permit Number - T15CM07646
Review Name: PLANS OK TO SUBMIT - RES
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/25/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 11/25/2015 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T15CM07646 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code, 2012 International Fire Code, 2011 National Electrical Code and Arizona Revised Statutes. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. DIAGRAMS / CALCULATIONS 1. Show a feeder conductor size for the distribution panel in compliance with Table 310.15(B)(16). Update the feeder protected by the 200 AMP breaker. The feeder size is also controlled by NEC 690.64 & 705.12 (D). If you have any questions please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 11/25/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved |