Permit Number: T15CM07631
Parcel: 137055230

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM07631
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2015 KEN BROUILLETTE FIRE REVIEW Approved
11/27/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/30/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments, also provide a written response.
#1. Please indicate the size and type of the GEC on the AC side per note #5 of the Riser diagram notes plan sheet PV -1.
#2. Please show the location and types of the DC disconnects on the riser diagram . NEC 690.13.
#3. Please clarify or show the inverter locations on the plan, sheet PV-3, as indicated per note 15 on the riser diagram notes plan sheet PV-1.
Ref: IBC 107.2.1. NEC 690.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2015 KROBLES1 OUT TO CUSTOMER Completed