Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T15CM07631
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/09/2015 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 11/27/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/30/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments, also provide a written response. #1. Please indicate the size and type of the GEC on the AC side per note #5 of the Riser diagram notes plan sheet PV -1. #2. Please show the location and types of the DC disconnects on the riser diagram . NEC 690.13. #3. Please clarify or show the inverter locations on the plan, sheet PV-3, as indicated per note 15 on the riser diagram notes plan sheet PV-1. Ref: IBC 107.2.1. NEC 690. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/23/2015 | KROBLES1 | OUT TO CUSTOMER | Completed |