Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM07613
Parcel: 13321074A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM07613
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/04/2015 MARTIN BROWN FIRE REVIEW Approved
11/18/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide or indicate on the plans how the bathroom exhaust fans EF1 and EF2 are to be independently controlled, as the lighting plan sheet E-101 does not reflect this. See HVAC note #1 on plan sheet M-101.
Ref: IBC sec 107.2.1.
11/23/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G-001; VICINITY MAP: THIS MAP DOES NOT INDICATE THE PROJECT SITE. PLEASE REVISE.
2. SHEET SV-101: THE INFORMATION ON THIS SHEET IS INCOMPLETE. PLEASE ADD THE INFORMATION.
3. SHEET A-101; WALL CONSTRUCTION LEGEND: THERE ARE SEVERAL WALL TYPES THAT ARE NOT USED ON THIS PLAN AND SHOW UP (VERY LIGHTLY) IN THE WALL CONSTRUCTION LEGEND. PLEASE DELETE THESE.
4. SHEET A-111; CEILING FINISH KEY; SYMBOLS LEGEND: THERE ARE SEVERAL ENTRIES THAT ARE NOT USED ON THIS PLAN AND SHOW UP (VERY LIGHTLY) IN THESE TABLES. PLEASE DELETE THESE.
5. SHEET A-121; FINISH SCHEDULE: THERE ARE SEVERAL ENTRIES THAT ARE NOT USED ON THIS PLAN AND SHOW UP (VERY LIGHTLY) IN THIS TABLE. PLEASE DELETE THESE.
6. SHEET S-100; ROOF FRAMING PLAN NOTES: THE FIFTH NOTE INDICATES JOISTS ARE DESIGNED FOR RTU SUPPORT. PLEASE PROVIDE A CALCULATION OR A REFERENCE DRAWING INDICATING THE EXISTING JOISTS AND BEAMS CAN SAFELY SUPPORT THESE NEW MECHANICAL LOADS.
7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/24/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
11/24/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
11/24/2015 ROBERT SHERRY WATER REVIEW Completed
11/24/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. The rooftop detail on sheet M-201 calls for a factory roof curb but the structural detail on sheet S-100 utilizes wood sleepers in addition to the unit curb. Coordinate the method used to mount the new rooftop units with the structural engineer. Reference: Section 107.2.1, IBC 2012.
3. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or below grade in an area capable of absorbing the condensate flow without surface drainage. The roof drains on this building terminate at the building wall and do not connect to a storm drain system. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson.
4. Verify that building automation system has the ability to automatically adjust the daily start-up time of the HVAC system based on the outside weather conditions. Reference: Section C403.2.4.3.3, IECC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2015 AROMERO4 APPROVAL SHELF Completed
12/08/2015 AROMERO4 OUT TO CUSTOMER Completed
12/08/2015 AROMERO4 REJECT SHELF Completed