Permit Number: T15CM07612
Parcel: 11618380A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM07612
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/23/2015 KEN BROUILLETTE FIRE REVIEW Approved
12/10/2015 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please clarify the square footage calculation for the proposed use of the building. Although the occupancy of the site is educational, the use of the building is business and should be calculated at 100 square feet per occupant. The maximum occupant load will be limited to a building use, Table 1004.1.2.
2. Please correct the exits required. There do not appear to be any classrooms included in this design.
12/10/2015 CLAYTON TREVILLYAN PLUMBING-COMMERCIAL REVIEW Passed
12/10/2015 CTREVIL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/11/2015 CLAYTON TREVILLYAN MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Please provide the minimum required ventilation for all corridors located in this building including the space directly adjoining the restrooms, Table 403.3