Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM07560
Parcel: 10706002K

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T15CM07560
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/15/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change As designed, the flow control fitting still needs to be removed from the building drain for cleaning. In addition, the vent for the flow control fitting may not be connected to the vent for the hydromechanical grease interceptor less than 6" above the flood rim of the hydromechanical grease interceptor. Reference: Section 905.5, IPC 2012. [Initial comment: Clarify how access is to be provided to the flow control device. Reference: Section 1003.4.2, IPC 2012.]
01/15/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/20/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: 902 W. Miracle Mile
T15CM7560
Building Plan (2nd Review)

TRANSMITTAL DATE: January 21, 2016

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The proposed building expansion requires a development package to be submitted and approved prior to the building plan.

3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
01/27/2016 LOREN MAKUS ENGINEERING REVIEW Reqs Change Development Package must be approved first.