Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T15CM07501
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/23/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G001; CODE ANALYSIS: PLEASE REVISE THE ACCESSIBILITY CODE TO THE 2009 EDITION AND REVIEW THE PLANS FOR CONFORMANCE. 2. SHEET A200: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE HARDWARE SCHEDULE. 3. SHEET A200; FLOOR PLAN: THE ENLARGED PLAN AT THE BAR REFERENCES 1/A702. PLEASE REVISE THAT REFERENCE. 4. SHEET A200 (FLOOR PLAN); SHEET A701: PLEASE INDICATE THE ENLARGED BAR PLAN 2/A701 ON THE FLOOR PLAN 1/A200. 5. SHEET A400: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE FINISH SCHEDULE. 6. GENERAL: PLEASE PROVIDE THE EXPIRATION DATE OF THE REGISTRATION BELOW THE SEAL OF THE DESIGN PROFESSIONAL ON EVERY SHEET. 7. GENERAL: PLEASE INDICATE ON THE DRAWINGS HOW THE REQUIREMENTS OF THE IBC SECTION 3411.7(1) ARE MET. INCLUDE THE SPECIFIC ITEM DESCRIPTION AND THE COST FOR THAT ITEM. 8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 11/23/2015 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Verify the size of the existing water meter serving this address, provide the serial number for the meter, and provide the water demand served by the water meter. 2. Provide the size of the reduced pressure backflow prevention assembly serving this building. Reference: Section 107.2.1, IBC 2012. |
| 11/23/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Appliances (e.g. coffee and tea dispensers, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1, 608.3 and 608.16.10, IPC 2012. 2. Water supply connections to carbonated beverage dispensers shall be protected with backflow preventers conforming to ASSE 1022. Reference: Section 608.16.1 and Table 608.1, IPC 2012. 3. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 4. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Exception: indirect waste piping conveying only clear-water waste (e.g. effluent from a sanitizing compartment) does not require a trap. Reference: Section 802.2, IPC 2012. |
| 11/23/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the plan for the walk-in meat cooler; on sheet D100 it is being removed, on sheet A400 it is shown with new resilient sheet flooring (and per keynote 27, apparently with new restroom partitions). On sheet MP100 it becomes a walk-in freezer. |
| 12/03/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |