Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2015 SHARPER BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 11-18-2015
Activity: T15CM07480
Address: 2905 E. Lester Rd.
Applicant: J. Mark, Straw Dogs Construction

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code and local amendments. In order to facilitate a shorter back check time, we request that you provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions and concerns before permit approved



1. Specify the roof sheathing to be installed on the new roof area, size, grade , nailing , thickness and. Type. R904

2. Underlayment installed on solid sheathing must be double per 905.2.7 correct section A sheet A-4 and details 1 and 2 sheet A-5.

3. Provide truss designs and calculations or note on the plans deferred submittal of truss documents to be provided prior to permit issuance.



Steven Harper
City of Tucson
Planning & Development Services