Permit Number: T15CM07303
Parcel: 136406740

Address:
9620 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM07303
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2015 STEVE SHIELDS ZONING REVIEW Completed
11/09/2015 ROBERT SHERRY WATER REVIEW Completed
11/09/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Lined water heaters with a heat input of 200,000 BTU per hour or more, an operating water temperature of 210ยบ F or greater, or a nominal water containing capacity of 120 gallons or more are required to comply with the rules contained in Article 4 (Arizona Boilers and Lined Hot Water Heaters) of the Arizona Administrative Code.
2. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
3. Provide third-party listing and material standards for all plumbing fixtures being provided by others (e.g. SK-2). Reference: Sections 303.4 and 402, IPC 2012.
11/10/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Demonstrate energy code compliance for the alterations to the building envelope based on the current code. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.
3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Use the exterior design conditions shown in Section 302.2, IECC 2012, as modified by the City of Tucson. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012.
4. Provide structural calculations to verify that the installation of the four new rooftop units will not adversely affect the structural integrity of the roof. Reference: Section 302.1, IMC 2012.
5. Provide calculations to show how ventilation will be provided for the occupied spaces. Reference: Sections 401.2 and 403.3, IMC 2012.
11/16/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET CS1.0; BUILDING REQUIREMENTS: CODE SECTIONS 506.3 AND 507.3 ARE REFERENCED FOR THE FIRE SPRINKLER REQUIREMENTS. THE IBC SECTION 903.2.7 WOULD BE THE ACTUAL SECTION THAT ADDRESSES SPRINKLER REQUIREMENTS. PLEASE REVISE.
2. SHEET CS1.0; BUILDING REQUIREMENTS: CODE TABLE 1018.1 IS REFERENCED FOR THE NUMBER OF EXITS REQUIREMENTS. THE IBC TABLE 1015.1 WOULD BE THE ACTUAL TABLE THAT ADDRESSES THE NUMBER OF EXITS REQUIREMENTS. PLEASE REVISE.
3. SHEET CS1.0; BUILDING REQUIREMENTS: CODE TABLE 1016.1 IS REFERENCED FOR THE MAXIMUM TRAVEL DISTANCE REQUIREMENT. PLEASE REVISE THE TABLE REFERENCE TO 1016.2.
4. SHEET HC1.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
5. SHEET D1.0; FLOOR PLAN: PLEASE CLEAR UP THE NOTES AND THE ROOM NUMBERS ON THE PLAN AT THE NORTH END.
6. SHEET D1.0; FLOOR PLAN: A SECTION CUT ON THE SOUTH WALL INDICATES 3/A2.0. PLEASE REVISE THE SHEET NUMBER.
7. GENERAL; SHEETS CS1.0 THROUGH SP6: ALL PROFESSIONAL SEALS MUST INCLUDE THE DATE THE SEAL WAS SIGNED AND THE EXPIRATION DATE FOR THAT LICENSE (BELOW THE SEAL).
8. GENERAL; SHEETS S101 THROUGH S402: ALL PROFESSIONAL SEALS MUST INCLUDE THE EXPIRATION DATE FOR THAT LICENSE (BELOW THE SEAL).
9. GENERAL: SHEET HC1.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE ALL SHEETS THAT DO NOT MEET THAT CRITERIA.
10. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/16/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved