Permit Number: T15CM07265
Parcel: 14118001G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM07265
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2015 MARTIN BROWN FIRE REVIEW Approved
10/29/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET COVER; APPLICABLE CODES: THE CURRENT ELECTRICAL CODE IS THE 2011 EDITION OF THE NEC. PLEASE REVISE.
2. SHEET F-1 (CANOPY); STRUCTURAL CALCULATIONS (SHEET 5): THE CALCULATIONS INDICATE A 7.25' X 7.25' SQUARE FOOTING, WHILE DETAIL 5 INDICATES A 7'-0" SQUARE FOOTING. PLEASE CLARIFY.
3. SHEET F-1 (CANOPY); STRUCTURAL CALCULATIONS (SHEET 46): THE CALCULATIONS INDICATE THE ANCHOR BOLTS REQUIRE 38" MINIMUM EMBEDMENT, WHILE THE DETAIL 5 INDICATES 20" MINIMUM EMBEDMENT. PLEASE CLARIFY.
4. SHEET 4 OF 6 (CANOPY): REVISE THIS DRAWING NUMBER TO A-2.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/04/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please change the applicable code for the NEC to 2011, on the cover plan sheet. There is no 2012.
11/05/2015 MICHAEL ST. PAUL ZONING REVIEW Reqs Change Approval of DP15-0172 is required. These plans must match the approved development package site plan.
11/10/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/10/2015 ELIZABETH LEIBOLD ENGINEERING REVIEW Reqs Change Grading Permit is not yet approved, so bldg permit can not be approved.
11/10/2015 ROBERT SHERRY WATER REVIEW Completed
11/12/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The minimum dimension for a secondary drain (e.g. a scupper) is 4". Reference: Section 1108.3, IPC 2012.
2. Provide a cleanout at the base of each roof drain stack prior to connection to the horizontal storm drain. Reference: Sections 708.3.4 and 1101.8, IPC 2012.
3. The material for storm drain pipes located under buildings (i.e. under the fuel canopy) shall conform to one of the standards listed in Table 702.2, IPC 2012. Reference: Section 1102.3, IPC 2012.