Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T15CM07231
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2015 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/05/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/12/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please clarify why Plan Sheet E2.8 shows Electrical Service "A" and "B1", "B2" as NEW and all the other Plan Sheets show them as existing. Also the PV OCPD;S ( FUSE ) sizes , do not correlate with the one and or three lines diagrams on the other plans. Ref: IBC sec. 107.2.1 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/03/2015 | AROMERO4 | OUT TO CUSTOMER | Completed |