Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM07231
Parcel: 13710512A

Address:
5660 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM07231
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2015 MARTIN BROWN FIRE REVIEW Approved
11/05/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/12/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please clarify why Plan Sheet E2.8 shows Electrical Service "A" and "B1", "B2" as NEW and all the other Plan Sheets show them as existing. Also the PV OCPD;S ( FUSE ) sizes , do not correlate with the one and or three lines diagrams on the other plans.
Ref: IBC sec. 107.2.1

Final Status

Task End Date Reviewer's Name Type of Review Description
12/03/2015 AROMERO4 OUT TO CUSTOMER Completed