Permit Number: T15CM07220
Parcel: 13112028A

Address:
6044 E 30TH ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM07220
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G1; AREA SUMMARY; BUILDING EXPANSION: THE AREA SUMMARY INDICATES THE EXISTING CHRPA OFFICE IS 825 SF (MATCHES SITE PLAN), WHILE THE BUILDING EXPANSION INDICATES THE EXISTING CHRPA OFFICE (PER T05CM06258) IS 886 PSF. PLEASE CLARIFY.
2. SHEET G1; BUILDING EXPANSION; SITE PLAN: THE BUILDING EXPANSION INDICATES THE TOTAL SF FOR THE CHRPA OFFICE IS 1626 SF, WHILE THE SITE PLAN INDICATES THE TOTAL SF TO BE 1565 SF. PLEASE CLARIFY.
3. SHEET G1; BUILDING CODE INFORMATION: THE ACTUAL AREA FOR THE CHRPA OFFICE IS LISTED HERE AS 1515 SF. PLEASE COORDINATE ALL OF THE SF NUMBERS LISTED ON THIS SHEET.
4. SHEET G1; BUILDING CODE INFORMATION: THE TRAVEL DISTANCE IS LISTED HERE AS 300 FEET. PER THE IBC TABLE 1016.2, THE ALLOWABLE MAXIMUM EXIT ACCESS TRAVEL DISTANCE IS 200 FEET (B OCCUPANCY TYPE WITH NO SPRINKLERS). PLEASE REVISE.
5. SHEET G1; BUILDING CODE INFORMATION (TOILET FACILITIES NOTES): UNDER THESE NOTES, PLEASE ADD A NOTE INDICATING A DRINKING FOUNTAIN IS NOT REQUIRED PER TABLE 2902.1, NOTE f.
6. SHEET A2: PLEASE PROVIDE SIGNED/SEALED STRUCTURAL CALCULATIONS FOR THIS ADDITION.
7. SHEET A2; GENERAL FOUNDATION NOTES: PROVIDE A NOTE ON THE DRAWING INDICATING THE ASSUMED SOIL BEARING CAPACITY VALUE PER THE IBC.
8. SHEET A2; ROOF FRAMING NOTES: NOTE 2 REFERENCES STRUCTURAL DETAILS ON SHEET S.1. PLEASE REVISE THE NOTE AND ADD THE DETAIL ON THE DRAWING.
9. SHEET A2; ROOF FRAMING NOTES: NOTE 7 REFERENCES STRUCTURAL DETAILS ON SHEETS S.1 AND S.2. PLEASE REVISE THE NOTE AND ADD DETAILS AS REQUIRED.
10. SHEET A2; ROOF FRAMING NOTES: REMOVE NOTE 11 FOR GLUE-LAMINATED BEAMS.
11. GENERAL: THE SUBMITTED ROOF TRUSS DRAWINGS FROM MITEK MUST BE REVIEWED BY THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
12. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/17/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
11/18/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2015 AROMERO4 OUT TO CUSTOMER Completed