Permit Number: T15CM07215
Parcel: 117033090

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM07215
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
10/16/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/16/2015 STEVE SHIELDS ZONING REVIEW Approved
10/16/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide energy code data for the new windows.
10/16/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PLEASE VERIFY THE 4" VENT AND THE 1 1/4" WATER LINE INDICATED ON SHEET P1.0 ARE LOCATED IN THE NEW METAL STUD WALL, OR VERIFY THE FIRE RATED WALL ASSEMBLY FOR THE ELEVATOR IS MAINTAINED. THE NEW METAL STUD WALL WOULD REQUIRE A 6" STUD TO ACCOMODATE THE 4" VENT. VERIFY EXISTING CAULKING IS RATED IF THE LINES ARE IN THE ELEVATOR WALL.
10/16/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how the new 4" stack relates to the existing 1st floor drain piping.
10/16/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/16/2015 ROBERT SHERRY WATER REVIEW Completed
10/19/2015 KROBLES1 FIRE REVIEW Needs Review