Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/16/2015 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
10/16/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide energy code data for the new windows. |
10/16/2015 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
10/16/2015 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
10/16/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PLEASE VERIFY THE 4" VENT AND THE 1 1/4" WATER LINE INDICATED ON SHEET P1.0 ARE LOCATED IN THE NEW METAL STUD WALL, OR VERIFY THE FIRE RATED WALL ASSEMBLY FOR THE ELEVATOR IS MAINTAINED. THE NEW METAL STUD WALL WOULD REQUIRE A 6" STUD TO ACCOMODATE THE 4" VENT. VERIFY EXISTING CAULKING IS RATED IF THE LINES ARE IN THE ELEVATOR WALL. |
10/16/2015 | ROBERT SHERRY | WATER | REVIEW | Completed | |
10/16/2015 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show how the new 4" stack relates to the existing 1st floor drain piping. |
10/16/2015 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
10/19/2015 | KROBLES1 | FIRE | REVIEW | Needs Review |