Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T15CM07120
Parcel: 105110660

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T15CM07120
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Footnote b on Table 403.3 states that mechanical exhaust is required for the kitchen and no air from the kitchen may be recirculated to any other space. HP-2 appears to be recirculating air from the kitchen to the corridor, service counter, and to the public restrooms. Reference: Section 403.2.1 (3), IMC 2012.
11/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/02/2015 EGALLET1 OUT TO CUSTOMER Completed