Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/19/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/02/2015 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Footnote b on Table 403.3 states that mechanical exhaust is required for the kitchen and no air from the kitchen may be recirculated to any other space. HP-2 appears to be recirculating air from the kitchen to the corridor, service counter, and to the public restrooms. Reference: Section 403.2.1 (3), IMC 2012. |