Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/02/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Footnote b on Table 403.3 states that mechanical exhaust is required for the kitchen and no air from the kitchen may be recirculated to any other space. HP-2 appears to be recirculating air from the kitchen to the corridor, service counter, and to the public restrooms. Reference: Section 403.2.1 (3), IMC 2012.
11/02/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed