Permit Number: T15CM07120
Parcel: 105110660

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T15CM07120
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2015 DAVID RIVERA ZONING REVIEW Approved
10/14/2015 PAUL BAUGHMAN ENGINEERING REVIEW Approved
10/16/2015 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/16/2015 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
10/16/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET M2.0; DETAIL 105: PLEASE PROVIDE STRUCTURAL CALCULATIONS TO VERIFY THE EXISTING ROOF STRUCTURE WILL SAFELY SUPPORT THE NEW HOOD.
2. SHEET M2.0; DETAIL 105: PLEASE PROVIDE A DETAIL ON THE DRAWING THAT INDICATES HOW THE DUCT SUPPORT IS CONNECTED TO THE STRUCTURE ABOVE. INCLUDE ALL FRAMING SIZES AND CONNECTIONS.
10/16/2015 ROBERT SHERRY WATER REVIEW Completed
10/16/2015 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
10/16/2015 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
10/19/2015 KEN BROUILLETTE FIRE REVIEW Approved